i) The building requirements, building services, specifications and standards specified in the National Building Code, 2005 shall be complied with.
ii) Construction of such buildings shall be undertaken by owners by engaging registered architect, licenced builder, fire engineer and licenced structural engineer. The designs and building plans shall be countersigned by the owner, licenced builder, registered architect, licenced engineer, qualified & licenced structural Engineer and a fire engineer who shall be responsible for the supervision, structural safety, fire safety and compliance of the specifications for such buildings.
iii) Buildings shall be designed for earth quake resistance and resistance for other natural hazards. The Completion Certificate obtained from the registered architect shall mention that the norms have been followed in the design and construction of buildings for making the buildings earthquake resistant, compliance with structural safety and fire safety requirements as per the relevant provisions of National Building Code & A.P Fire Services Act.
iv) The exit and fire safety requirements shall be in accordance with Part-IV of National Building Code of India. The fire safety measures shall be undertaken by engaging the services of a fire protection engineer. The following minimum Fire Fighting Installations are to be provided as per Table 23, Part - 4 of National Building Code of India, 2005:
| Sl.No | Fire Fighting Installation |
|---|---|
| 1. | Fire Extinguishers as per IS 2190 |
| 2. | Hose reel |
| 3. | Wet riser |
| 4. | Yard hydrant |
| 5. | Automatic sprinkler system in entire Building |
| 6. | Automatic detection and alarm system in entire Building (except Cellars) |
| 7. | Manually operated electrical alarm system in entire Building (except Cellars) |
| 8. | Underground static water tank of 2,00,000 Liters capacity |
| 9. | Terrace tank of 20,000 Liters capacity |
| 10. | Two Electrical Main pumps of 2850 LPM capacity |
| 11. | Diesel pump (Standby of 2850 LPM capacity |
| 12. | Electric Jockey pump of 180 LPM capacity |
v) The work of other building services like sanitation, plumbing, lifts, electrical installations, and other utility services shall as per National Building Code standards and shall be executed under the planning, design and supervision of qualified and competent technical personnel.
vi) The means of escape shall be provided as per the Clause 4 (Exit Requirements), Part 4 of National Building Code of India.
(a) Capacities of Exits shall be calculated as per Clause 4.4, Part 4 of NBC, 2005.
(b) Arrangement of Exits shall be as per Clause 4.5, Part 4 of NBC, 2005.
(c) Number of Exits shall be provided as per Clause 4.6, Part 4 of National Building Code, 2005.
(d) Doorways shall be provided as per Clause 4.7, Part 4 of National Building Code, 2005.
(e) Corridors and Passageways shall be provided as per Clause 4.8, Part 4 of National Building Code, 2005.
(f) Internal Staircases shall be provided as per Clause 4.9, Part 4 of National Building Code, 2005.
(g) Pressurization of Staircases shall be provided as per Clause 4.10, Part 4 of National Building Code, 2005.
(h) External Staircases shall be provided as per Clause 4.11, Part 4 of National Building Code, 2005.
(i) Horizontal Exits may be provided as per Clause 4.12, Part 4 of National Building Code, 2005.
(j) Fire Tower shall be provided as per Clause 4.13, Part 4 of National Building Code, 2005.
(k) Ramps shall be provided as per Clause 4.14, Part 4 of National Building Code, 2005.
(l) Fire Lift shall be provided as per Clause 4.15, Part 4 of National Building Code, 2005.
(m) Emergency and Escape Lighting shall be provided as per Clause 4.16, Part 4 of National Building Code, 2005.
(n) Illumination of Means of Exit shall be provided as per Clause 4.17, Part 4 of National Building Code, 2005.
(o) Fire Detection and Warning shall be provided as per Clause 4.18, Part 4 of National Building Code, 2005
vii) "SMOKE MANAGEMENT: The following measures are to be provided to prevent the spread of smoke easily to the other floors, which may affect the life safety of the occupants particularly, the Cinema viewers;
(A) For Types 1 to 3 constructions as given Clause 3.3 in the National Building Code (Part-IV), a doorway or opening in a separating wall on any floor shall be limited to 5.6m 2 in area with a maximum height/width of 2.75 m. Every wall opening shall be protected with fire-resisting doors having the fire rating of not less than 2 h in accordance with accepted standard [4(7)].All openings in the floors shall be protected by vertical enclosures extending above and below such openings, the walls of such enclosures having a fire resistance of not less than 2 h and all openings therein being protected with a fire resisting assembly as specified in clause 3.4.8 & 3.4.9 of Part-4 of NBC.
(B) Openings in walls or floors which are necessary to be provided to allow passages of all building services like cables, electrical wirings, telephone cables, plumbing pipes,etc,shall be protected by enclosure in the form of ducts/shafts having a fire resistance not less than 2 h. The inspection door for electrical shafts/ducts shall not be less than2 h and for other services shafts/ducts, the same shall have fire resistance not less than 1 h. Medium and low voltage wiring running in shafts/ducts, shall either be armored type or run through metal conduits. Further, the space between the conduits pipes and the walls / slabs shall be filled in by a filter material having fire resistance rating of not less than 1 h as per clause 3.4.8.3 of Part-4 of National Building Code.
(C) Openings in separating walls and floors-Attention shall be paid to all such factors as will limit fire spread to these opening and maintain fire rating of the structural member. Every wall opening shall be protected with Fire resisting doors having fire rating of not less than two hours. All openings in the floors shall be protected by vertical enclosures extending above and below such openings, the wall of such enclosures having a fire resistance of not less than two hours and all openings therein being protected with a fire resisting assemble as per Clause 3.4.8, Part 4 of National Building Code of India,2005.
(D) Every vertical opening between the floors shall be suitably enclosed or protected, as necessary to provide the following:
i) Reasonable safety to the occupants while using the means of egress by preventing spread of fire, smoke, or fumes through vertical openings from floor to floor to allow occupants to complete their use of the means of egress. Further it shall be ensured to provide a clear height of 2100 MM in the passage/escape path of the occupants.
(E)
(F)
7.6.
ii) Limitation of damage to the building and its contents (Clause 3.4.8.4) Part -- 4 of National Building Code of India, 2005.
Where openings are permitted, they shall not exceed three-fourths the area of the wall in the case of an external wall and they shall be protected with fire resisting assemblies or enclosures having fire resistance equal to that of the wall or floor in which these are situated. Such assemblies and enclosures shall also be capable of preventing the spread of smoke or fumes through the openings so as to facilitate the safe evacuation from the building in case of fire.
(i) Air conditioning and ventilating systems shall be so installed and maintained as to minimize the danger of spread of fire, smoke or fumes from one floor to other or from outside to any occupied building or structure (Clause 3.4.11.1) Part 4 of National Building Code of India 2005.
(ii) Air-conditioning and ventilating systems circulating air to more than one floor or fire area shall be provided with dampers designed to close automatically in case of fire and thereby preventing spread of fire or smoke and shall be in accordance with the accepted standard [4(10)]. Such a system shall also be provided with automatic controls to stop fans in case of fire, unless arranged to remove smoke from a fire, in which case these shall be designed to remain in operation
(iii) Effective means for preventing circulation of smoke through the A C system in case of fire in air filters or from other sources drawn into the system, and shall have smoke sensitive devices for actuation in accordance with the accepted standards (Clause 3.4.11.3) Part 4 of National Building Code of India 2005.
(iv) Separate air handling units for each floor shall be provided to avoid the hazards arising from spread of fire and smoke through air conditioning ducts (Clause 3.4.11.4) Part 4 of National Building Code of India 2005.
(v) Fire Dampers shall be provided in the AC system in accordance with the accepted standards designed so as to close automatically in case of fire and thereby preventing spread of fire or smoke.
(G) Pressurization of stair cases shall be done as per Clause 4.10, Part 4 of National Building Code of India 2005.
(H) Provision of pressurized lift lobby with self-closing smoke stop doors of 2 hour Fire resistance, one in the lift lobbies of all the cellars.
(I) Smoke venting facilities for safe use of exits shall be provided as per Clause 3.4.12, Part 4 of National Building Code of India 2005.
(J) Basement ventilation shall comply to Clause C 1.6 of Annexure-C of Part 4 of National Building Code of India, 2005.