| Mechanical Permit Checklist MECHANICAL Checklist | Mechanical Permit Checklist MECHANICAL Checklist | Mechanical Permit Checklist MECHANICAL Checklist | Mechanical Permit Checklist MECHANICAL Checklist | Mechanical Permit Checklist MECHANICAL Checklist | Mechanical Permit Checklist MECHANICAL Checklist | Mechanical Permit Checklist MECHANICAL Checklist | Mechanical Permit Checklist MECHANICAL Checklist |
| 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms |
| Project Address | Project Address | Project Address | Project Address | Project Address | Project Address | Date | Date |
| The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. | The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. | The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. | The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. | The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. | The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. | The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. | The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. |
| Applicability (yes, no, n.a.) | Applicability (yes, no, n.a.) | Applicability (yes, no, n.a.) | Code Section | Component | Information Required | Location on Plans | Building Department Notes |
| HEATING, VENTILATION, AND AIR CONDITIONING (Chapter 5) | HEATING, VENTILATION, AND AIR CONDITIONING (Chapter 5) | HEATING, VENTILATION, AND AIR CONDITIONING (Chapter 5) | HEATING, VENTILATION, AND AIR CONDITIONING (Chapter 5) | HEATING, VENTILATION, AND AIR CONDITIONING (Chapter 5) | HEATING, VENTILATION, AND AIR CONDITIONING (Chapter 5) | HEATING, VENTILATION, AND AIR CONDITIONING (Chapter 5) | HEATING, VENTILATION, AND AIR CONDITIONING (Chapter 5) |
| MANDATORY PROVISIONS (Section 5.2) | MANDATORY PROVISIONS (Section 5.2) | MANDATORY PROVISIONS (Section 5.2) | MANDATORY PROVISIONS (Section 5.2) | MANDATORY PROVISIONS (Section 5.2) | MANDATORY PROVISIONS (Section 5.2) | MANDATORY PROVISIONS (Section 5.2) | MANDATORY PROVISIONS (Section 5.2) |
| 5.2.2 | Equipment efficiency | Provide equipment schedule with type, capacity, efficiency | |||||
| 5.2.3 | Controls | ||||||
| 5.2.3.1 | Time clocks | Indicate thermostat with night setback, 3 different day types, and 2-hour manual override | |||||
| 5.2.3.2 | Temp. & dead band | Indicate temperature control with 3 degree C deadband minimum | |||||
| 5.2.3.3 | Cooling tower, fluid cooler | Indicate two-speed motor, pony motor, or variable speed drive to control the fans | |||||
| 5.2.4.1 | Piping & ductwork | ||||||
| 5.2.4.1 | Piping insulation | Indicate R-value of insulation | |||||
| 5.2.4.1 | Ductwork insulation | Indicate R-value of insulation | |||||
| 5.2.4.1 | Ductwork sealing | Specify sealing types and locations | |||||
| 5.2.4 | System balancing | Specify system balancing | |||||
| PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) | PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) | PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) | PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) | PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) | PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) | PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) | PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) |
| 5.3 | Indicate whether project is complying with ECBC Prescriptive Option OR with ASHRAE Standard 90.1-2004 | ||||||
| 5.3.1 | Economizer | ||||||
| 5.3.3.1 | Air economizer | Indicate 100% capability on schedule | |||||
| 5.3.3.2 | Integrated operation | Indicate capability for partial cooling | |||||
| 5.3.3.3 | Field testing | Specify tests | |||||
| 5.3.2 | Variable flow hydronic | ||||||
| 5.3.3.1 | Pump flow rates | Indicate variable flow capacity on schedules | |||||
| 5.3.3.2 | Isolation valves | Indicate two-way automatic isolation valves | |||||
| 5.3.3.3 | Variable speed drive | Indicate variable speed drive | |||||
| SERVICE WATER HEATING AND PUMPING (Chapter 6) | SERVICE WATER HEATING AND PUMPING (Chapter 6) | SERVICE WATER HEATING AND PUMPING (Chapter 6) | SERVICE WATER HEATING AND PUMPING (Chapter 6) | SERVICE WATER HEATING AND PUMPING (Chapter 6) | SERVICE WATER HEATING AND PUMPING (Chapter 6) | SERVICE WATER HEATING AND PUMPING (Chapter 6) | SERVICE WATER HEATING AND PUMPING (Chapter 6) |
| MANDATORY PROVISIONS (Section 6.2) | MANDATORY PROVISIONS (Section 6.2) | MANDATORY PROVISIONS (Section 6.2) | MANDATORY PROVISIONS (Section 6.2) | MANDATORY PROVISIONS (Section 6.2) | MANDATORY PROVISIONS (Section 6.2) | MANDATORY PROVISIONS (Section 6.2) | MANDATORY PROVISIONS (Section 6.2) |
| 6.2.1 | Solar water heating | Provide calculations to justify capacity to meet 20% threshold | |||||
| 6.2.2 | Equipment efficiency | Provide equipment schedule with type, capacity, efficiency | |||||
| 6.2.4 | Piping insulation | Indicate R-value of insulation | |||||
| 6.2.5 | Heat traps | Indicate heat trap on drawings or provide manufacturers specifications to show that equipment has internal heat trap | |||||
| 6.2.6 | Pool covers | Provide vapor retardant cover for pools | |||||
| 6.2.6 | Pools over 32°C | Provide R-2.1 insulation | |||||
15.5 Lighting Summary
| Lighting Summary | Lighting Summary | Lighting Summary | Lighting Summary | Lighting Summary |
| 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms | 2007 Energy Conservation Building Code Compliance Forms |
| Project Info Project Address Date For Building Department Use Applicant Name: Applicant Address: Applicant Phone: | Project Info Project Address Date For Building Department Use Applicant Name: Applicant Address: Applicant Phone: | Project Info Project Address Date For Building Department Use Applicant Name: Applicant Address: Applicant Phone: | Project Info Project Address Date For Building Department Use Applicant Name: Applicant Address: Applicant Phone: | Project Info Project Address Date For Building Department Use Applicant Name: Applicant Address: Applicant Phone: |
| Project Description New Addition Alteration Change of Use | Project Description New Addition Alteration Change of Use | Project Description New Addition Alteration Change of Use | Project Description New Addition Alteration Change of Use | Project Description New Addition Alteration Change of Use |
| Compliance Option Prescriptive Envelope Trade-Off (Appendix D) Whole Building Performance | Compliance Option Prescriptive Envelope Trade-Off (Appendix D) Whole Building Performance | Compliance Option Prescriptive Envelope Trade-Off (Appendix D) Whole Building Performance | Compliance Option Prescriptive Envelope Trade-Off (Appendix D) Whole Building Performance | Compliance Option Prescriptive Envelope Trade-Off (Appendix D) Whole Building Performance |
| Alterations Exceptions (Check box, if appropriate) Less than 50 % of fixtures are new and installed lighting wattage is not being increased | Alterations Exceptions (Check box, if appropriate) Less than 50 % of fixtures are new and installed lighting wattage is not being increased | Alterations Exceptions (Check box, if appropriate) Less than 50 % of fixtures are new and installed lighting wattage is not being increased | Alterations Exceptions (Check box, if appropriate) Less than 50 % of fixtures are new and installed lighting wattage is not being increased | Alterations Exceptions (Check box, if appropriate) Less than 50 % of fixtures are new and installed lighting wattage is not being increased |
15.6 Lighting Permit Checklist
| Lighting Permit Checklist LIGHTING Checklist | |||||||
| 2007 Energy Conservation Building Code Compliance Forms | |||||||
| Project Address | Date | ||||||
| The flowing information is necessary to check a building permit application for compliance with the building envelope requirements in the Energy Conservation Building Code, 2007. | |||||||
| Applicability (yes, no, n.a.) | Code Section | Component | Information Required | Location on Plans | Building Department Notes | ||
| LIGHTING (Section 7.2) | |||||||
| MANDATORY PROVISIONS (Section 7.2) | |||||||
| 7.2.1 | Lighting Controls | ||||||
| 7.2.1.1 | Automatic shutoff | Indicate automatic shutoff locations or occupancy sensors | |||||
| 7.2.1.2 | Space control | Provide schedule with type, indicate locations | |||||
| 7.2.1.3 | Daylight zones | Provide schedule with type and features, indicate locations | |||||
| 7.2.1.4 | Exterior lighting control | Indicate photosensor or astronomical time switch | |||||
| 7.2.1.5 | Additional control | Provide schedule with type, indicate locations | |||||
| 7.2.2 | Signage/Advertising Signage | Indicate 5 watts maximum | |||||
| 7.2.3 | Exterior Building grounds lighting | Indicate minimum efficacy of 60 lumens/Watt | |||||
| PRESCRIPTIVE INTERIOR LIGHTING POWER COMPLIANCE OPTION (Section 7.3) | |||||||
| 7.3 | Indicate whether project is complying with the Building Area Method (7.3.2) or the Space Function Method (7.3.3) | ||||||
| 7.3.2 | Building area method | Provide lighting schedule with wattage of lamp and ballast and number of fixtures. Document all exceptions. | |||||
| 7.3.3 | Space function method | Provide lighting schedule with wattage of lamp and ballast and number of fixtures. Document all exceptions. | |||||
15.7 Electrical Power (Section 8)
| MANDATORY PROVISIONS (Section 8.2) | |||||||
| 8.2.1 | Transform ers | Provide schedule with transformer losses | |||||
| 8.2.2 | Motor efficiency | Provide equipment schedule with motor capacity, efficiency | |||||
| 8.2.3 | Power factor correction | Provide schedule with power factor correction | |||||
| 8.2.4 | Check metering | Provide check metering and monitoring | |||||
3 For Exceptions to this clause please refer to Table 4.4 of APECBC.