7.3.1 Interior Lighting Power:
The installed interior lighting power for a building or a separately metered or permitted portion of a building shall be calculated in accordance with clause 7.3.4 and shall not exceed the interior lighting power allowance determined in accordance with either clause 7.3.2 or clause 7.3.3. Tradeoffs of interior lighting power allowance among portions of the building for which a different method of calculation has been used are not permitted:
Exception for 7.2.2.1: The following lighting equipment and application shall not be considered when determining the interior lighting power allowance, nor shall the wattage for such lighting be included in the installed interior lighting power. However, any such lighting shall not be exempt unless it is an addition to general lighting and is controlled by an independent control device,-
(a) Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments;
(b) Lighting that is integral to equipment or instrumentation and is installed by its manufacturer;
(c) Lighting specifically designed for medical or dental procedures and lighting integral to medical equipment;
(d) Lighting integral to food warming and food preparation equipment;
(e) Lighting for plant growth or maintenance;
(f) Lighting in spaces specifically designed for use by the visually impaired;
(g) Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions;
(h) Lighting in interior spaces that have been specifically designated as a
registered interior historic landmark;
(i) Lighting that is an integral part of advertising or directional signage
(j) Exit signs;
(k) Lighting that is for sale or lighting educational demonstration systems;
(l) Lighting for theatrical purposes, including performance, stage, and film or video production
(m) Athletic playing areas with permanent facilities for television broadcasting.
7.3.2 Building Area Method:
Determination of interior lighting power allowance (watts) by the building area method shall be in accordance with the following:
(a) Determine the allowed lighting power density from Table 7.1 for each appropriate building area type;
(b) Calculate the gross lighted floor area for each building area type; and