Part VGeneral Building Requirements (1) Classification
Classification of Buildings.- Buildings shall be classified on the basis of occupancy as follows :-
(a) Residential.
(b) Educational.
(c) Institutional.
(d) Assembly.
(e) Business.
(f) Mercantile (including both retail and wholesale stores).
(g) Industrial (including low, moderate and high fire hazards).
(h) Storage.
(i) Hazardous.
(II) Open Spaces (within a Plot)
General.- (1) Every room intended for human habitation shall abut on an interior or exterior open space or an open verandah open to such interior or exterior open space.
Rule 56
77
(2) Open spaces to cater for lighting and ventilation requirement: The open spaces inside or around building have essentially to cater for the lighting and ventilation requirements of the rooms abutting such open spaces and in the case of building abutting streets in the front, rear or sides, the open spaces provided shall be sufficient for the future widening of such streets.
(3) Open spaces separate for each building or wing: The open spaces shall be separate or distinct for each building and where a building has two or more wings, each wing shall have separate or distinct open spaces for the purposes of light and ventilation of the wings.
(4) Separation between accessory and main buildings of more than 7 meter in height shall not be less than 1.5 meters. For buildings up to 7 meters in height no such separation shall be required.
Construction of commercial complex -- Leaving space of 4.5 meter as off-street parking and 4.5 meter as open space, these are two different requirements which are to be fulfilled and cannot be clubbed together. Satish Nayak Vs. State of M.P. and others, 2018 (2) RN 1 (HC) 2018 Supreme 292 (MP).
Residential Buildings.-Open Spaces,- Exterior open spaces for buildings having height up to 12.5 meters.
(1) Front open spaces,-
(a) Every Residential Building having height up to 12.5 meters, facing street shall have a front open space mentioned below and such open space shall form an integral part of the site :-
S.No.
Width of street facing the plot
Front open space Min.
(1)
(2)
(3)
1.
Up to 9.0 meters
3.0 meters
2.
More than 9.0 meters and up to 12 meters
3.6 meters
3.
More than 12.0 meters and up to 18 meters
4.5 meters
4.
Above 18 meters
6.0 meters
(b) In existing developed areas with streets less than 6.0 meters in width, the distances of the building (building line) shall be at 6.0 meters from the center line of the street.
Rule 56
78
(2) Rear Open Space,-
(a) Every Residential Building, having height up to 12.5 meters, shall have a Rear Open Space, as below:-
S.No.
Plot area in Square meters
Minimum Rear Open space in meters
(1)
(2)
(3)
1.
Up to 40.00
Nil
2.
Above 40.00 and up to 150.00
1.50
3.
Above 150 and up to 225.00
2.50
4.
Above 225.00
3.00
(b) Rear open space to extend upto the rear wall : The rear open space shall be co-extensive with the entire face of the rear wall. If a building abuts on two or more streets, such rear open space shall be provided through-out the entire face of the rear wall. Such rear wall shall be the wall on the opposite side of the face of the building unless the Authority otherwise directs.
(3) Side open space-
Every semi-detached and detached building shall have a permanently open airspace on sides, forming integral part of the site as below :-
(i) For detached buildings there shall be minimum side open spaces of 3 meters on both the sides :
Provided that for detached residential building up to 7 meters in height on plots with a frontage less than 12 meters, one of the sides open space may be reduced to 1.5 meters.
(ii) For semi-detached building there shall be a minimum side open space of 3.0 meters on one side. For Semi-detached building up to 10 meters in height on plots with a frontage up to 10 meters, the side open space may be reduced to 2.5 meters.
(iii) For row-type buildings, no side open space is required.
(4) Notwithstanding anything contained in sub-rule (2) and (3) garage may be permitted at rear end of the side open space.
(5) Open space for building of more than 12.5 meters height - For building of height above 12.5 meters the open spaces around building shall be as given in Table 4 and 5 of Rule 42.
(6) Interior open spaces for all buildings,-
Rule 56
79
(a) Inner Courtyard,-
(i) Every room (except bath, water closet and store room) that does not abut on either the front, rear or side open spaces shall abut on an inner courtyard, having minimum side of 3 meters.
(ii) Further the inner courtyard shall have a minimum area, throughout its height, of not less than the square of one-fifth the height of the highest wall abutting the courtyard :
Provided that when any room (excluding staircase bay, bathroom and water closet) is dependent for its light and ventilation on an inner courtyard, its dimension shall be such as is required for each wing of the building.
(iii) Where only water closet and bath room are abutting on the interior courtyard, the size of the interior courtyard shall be in line with the provision for ventilation shaft as given in clause (b).
(b) Ventilation Shaft - For ventilating the spaces for water closet and bath room in all types and height of buildings, if not opening on the front or side or rear or interior open spaces, shall open on to the ventilation shaft, the size of which shall not be less than the values given below :-
Height of buildings
Size of ventilation shaft in
Minimum size of a side of
in meters
square meters
shaft in meters
(1)
(2)
(3)
Up to 10
1.2
0.9
12.5
2.8
1.2
18
4.0
1.5
24
5.4
1.8
30
8.0
2.4
above 30
9.0
3.0
Note 1: For buildings above 30 meters mechanical ventilation system, shall be installed besides the provision of minimum ventilation shaft.
Note 2: For fully air-conditioned residential buildings the ventilation shaft need not be insisted:
Provided that the air-conditioning system is designed to work in an un-interrupted manner which means that there is an alternate source of power supply.
(c) Outer Courtyard- The minimum width of outer courtyard (distinguished from its depth) shall be 2.4 meters. If the width of the outer courtyard is less than 2.4 meters, then it shall be treated as a notch and the provisions of outer courtyard shall not apply.
Rule 57
80
(III) Floor area and height limitation
Floor Area Ratio - The Floor Area Ratio (FAR) for different use group shall be as mentioned in Table 8 :-
TABLE 8
(See Rule 61)
FLOOR AREA RATIO FOR DIFFERENT USE GROUP
S.No.
Use Group
FAR*
Category
(1)
(2)
(3)
(4)
1.
Resdential
1.25
2.
Commercial
2.502.001.751.501.25
City Centre Sub-city center Community Center Local Shopping Centre Convenience Shopping Centre
3.
Public Semi-public
1.00
Administrative Areas / Education and Research/ Health/Social/Cultural/ Institutional
4.
Industrial
as per rule48
as per rule 48
* F.A.R and Density may be adopted as provided in the Development Plans of respective towns.
Rule 61
84
Note : (1) In case where the owner surrenders a portion of his plot / land and vests its ownership in the Government/Authority for public purpose, an additional floor area calculated adding twice the area of plot/land surrendered by him may be allowed in the remaining area of the plot/land in lieu of the monetary compensation.
(2) In case of in-situ redevelopment of a slum, an additional FAR upto 0.50 may be allowed in addition to the permissible FAR in that area, however all other norms related to the development and building permission shall be observed.
(3) On plot admeasuring 200 to 500 sq. meters one servant quarter and on plot admeasuring more than 500 sq. meters two servant quarters may be permitted, The size of a servant quarter shall not exceed 25 sq. m. and the area of the servant quarter shall not be counted in the built up area or the covered area.
(4) Covered parking with a clear height of 2.4 meters may be provided within the permissible ground coverage on plots measuring 1[200 sq.m.] or more. Such area of parking shall not be counted towards Floor Area Ratio and permissible height calculations.
(5) In case of redevelopment of areas in the old part of any city/town, the old and dilapidated structures may be reconstructed and if needed, an additional FAR up to an extent of 0.25 may be sanctioned over and above the permissible FAR of the area. However no other norm related to the development and building permission shall be relaxed.
(6) The total built up area of economically weaker section and low income group houses constructed to the extent provided for under the provisions of Madhya Pradesh Nagar Palik Nigam Adhiniyam 1956, Madhya Pradesh Nagar Palika Adhiniyam 1961 and Madhya Pradesh Panchayati Raaj Evam Gram Swaraj Adhiniyam 1993 and the rules made thereunder, shall not be counted towards the calculations of the floor area ratio. However such exemption shall be limited to the built up area of such EWS and LIG dwelling units as together constitute 15% of the number of dwelling units proposed to be developed in the same colony for other income groups.
2["(7) In addition to the FAR as mentioned in above said table, additional FAR as Premium Floor Area Ratio may be provided over and above which shall not exceed 25% of the Base FAR. The rate of such Premium FAR shall be as may be decided by the State Government."]
1 Subs. by Notification No. F. UDH-3/0002/18-5/2024 dated 06th March 2025.
Published in M.P. Rajpatra (Asadharan) S.N. 73 dated 06th March 2025 at pages 146-146(2).
2 Inserted by Notification No. F. UDH-3/0002/18-5/2024 dated 06th March 2025. Published in M.P. Rajpatra (Asadharan) S.N. 74 dated 06th March 2025 at pages 148(3)-148(10).
Rule 62-65
85
Corporation took possession of petitioners, lands and demolished their buildings without acquiring same and without even making payment of compensation to them -- Petitioners not ready and willing to surrender their land/properties in favour of Corporation -- Unilaterally invoking Rule 61, Corporation cannot be permitted to take possession of properties of petitioners which would tantamount to violation of Article 300-A of Constitution -- Corporation cannot be permitted to take possession of lands in question without acquiring same and without making payment of compensation. - Prem Narayan Patidar and others Vs. Municipal Corporation, Bhopal and others, 2014 (4) MPLJ 649.
Norms for Podium.- (1) Podium may be constructed,-
(a) on a plot admeasuring at least 1000 sq.mtrs.;
(b) in such manner that the clear height of each floor does not exceed 2.4 meters; and
(c) with a maximum of three such floors above ground level.
(2) Podium shall not be counted in the calculation of the Floor Area Ratio and the building height. The uncovered roof top portion of the podium shall be counted towards the requirement of open spaces prescribed under rule 47 and rule 60.
(3) The restriction of 2.4 meters clear height mentioned in sub-rule 1 (b) may be relaxed according to the design needs of mechanized parking. The maximum permissible height of the podium in such cases shall not exceed 2.4 m x 3 Floors + designed thickness of beams and slabs in Podium Parking Floor.
(4) The uncovered roof top portion of the podium may be used for development of uncovered park, water / swimming pool, parking.
Parking Floors.- Where the plot size is not less than 1000 sq. mtrs. covered parking with a clear height of not more than 2.4 meters may be permitted on any floor of the building according to the requirement of the project. Such parking shall not be included in the calculation of the FAR. If such parking is provided on the entire floor area, then such parking floor would not be included in the height of the building.
Service Floor.- Service floor may be provided in the building on plots having area 1000 square meters or more. The clear height of such service floor shall not exceed 2 meters and the same shall not be counted for the purpose of calculating Floor Area Ratio and the building height.
Height limit.- (1) The maximum height of a building shall be determined by the provision of Table No. 4 and 5 of Rule No. 42 as the case may be.
Rule 66
86
(2) If a plot abuts on two or more streets of different widths, the building shall be deemed to face such street which has greater width and the height of the building shall be regulated by the width of that street. This height may be continued to a depth of 24 meters along the narrower street.
(3) In case the building is located in vicinity of aerodromes, the maximum height of such building shall be such as determined by the Airport Authority.
Permission to build skyways and subways.- (1) The Authority may permit the construction of skyway at different levels connecting two or more buildings:
Provided that no such skyway shall be built,-
(a) below a height of 6.5 meters as measured from highest level of the ground immediately below the skyway. However, this may be relaxed by the Authority if the nature of the movement under the skyway so permits.
(b) across any public street without obtaining the prior permission of the agency responsible for its construction and maintenance;
(c) without obtaining prior permission of the Fire Authority and a certificate of structural safety from the licensed structural engineer;
(d) in a manner that may obstruct any vehicular movement under it;
(e) with a width of more than 4 meters; and
(f) if the columns supporting such skyway do not harmonize with the surrounding architectural features.
(2) The Authority may permit the construction of a subway (an underground passage for pedestrian and/or vehicular use) with the object of connecting two or more points:
Provided that a subway for the use of pedestrians shall be built,-
(a) sufficiently below the ground to enable safe passage of vehicular or pedestrian traffic over it;
(b) across a public street after obtaining prior permission of the agency responsible for its construction and maintenance;
(c) after obtaining prior permission of the Fire Authority and a certificate of structural safety from the licensed structural engineer;
(d) in a manner that ensures that the lighting, drainage, ventilation, signage, utilities and services are comfortable and safe for the usage of the people; and
(e) with a clear height and width of not less than 3.0 meters and 4.5 meters respectively.
Note : If the subway is expected to allow vehicular traffic, the design parameters shall be approved by the Authority on case to case basis keeping in view the safety and comfort of the users.
Rule 67-69
87
Plantation.- A plot having area of 100 square meters or more shall be planted with trees after the completion of construction of building. The number of trees planted shall be one tree for every 100 square meters of individual plot. The occupancy certificate for the building will be issued only when the authority is satisfied that the provisions of this rule have been complied with. Every effort shall be made to protect the existing trees on the plot.
(7) Joint open air space for buildings -
(a) Every interior or exterior open air space, unless the latter is a street, shall be maintained and shall lie entirely within the owner's own premises.
(b) If such interior or exterior open air space is intended to be used for the benefit of more than one building belonging to the same owner, then the width of such open air space shall be equal to the one as specified for tallest building abutting on such open air space.
(c) If such interior or exterior open space is jointly owned by more than one person, then its width shall be as per (b) above :
Provided that every such person agrees in writing to allow his portion of such joint open space to be used for the benefit of every building abutting on such joint open space and provided he submits his written consent to the Authority for record. Such common open space shall henceforth be treated as a permanently open space required for the purposes of these rules. No boundary wall between such joint open space shall be erected or raised to a height above 2.0 meters.
Open spaces for other occupancies.- In case where the development permission under section 29 or 16 is applied for the following occupancies/buildings :-
(a) Educational Buildings - Except for nursery school, the open spaces around the building shall be not less than 6 meters.
(b) Institutional Building - The open spaces around the building shall not be less than 6 meters.
(c) Assembly Building- The open space at front shall not be less than 12 meters and other spaces around the building shall not be less than 6 meters.
(d) Business, Mercantile and Storage Buildings - The open spaces shall not be less than 6 meters in the front and 4.5 meters on other three sides, Where these are situated in purely residential zone or residential with shops line zone, the open spaces may be relaxed.
(e) Industrial Buildings - The open spaces around the building shall not be less than 4.5 meters for heights up to 16 meters with an increase of the open spaces of 0.25 meters for every increase of 1 meter or fraction thereof in height above 16 meters.
(f) Hazardous occupancies - The open space around the building shall be as specified for industrial buildings mentioned in clause (e) above.
Rule 58
81
Construction of commercial complex -- Leaving space of 4.5 meter as off-street parking and 4.5 meter as open space, these are two different requirements which are to be fulfilled and cannot be clubbed together. Satish Nayak Vs. State of M.P. and others, 2018 (2) RN 1 (HC) = 2018 Supreme 292 (MP).
(IV) Requirements of parts of building
Plinth.- (1) Main Building : The plinth or any part of a building or out house shall be so located with respect to surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be more than 45 centimeters from the surrounding ground.
(2) Interior courtyard : Every courtyard shall be raised to ensure satisfactory drainage.
Habitable rooms.- (1) Height : The height of all rooms for human habitation shall not be less than 2.6 Meters measured from the surface of the floor to the lowest point of the ceiling (bottom of slab). In case of pitched roof, average height of rooms shall not be less than 2.6 meters. The minimum clear head room under a beam, folded plates or caves shall be 2.4 meters. In case of air-conditioned rooms a height of not less than 2.4 meters measured from the surface of the floor to the lowest point of airconditioning duct or the false ceiling shall be provided.
(2) The requirements of sub-rule (1) shall apply to residential, business and mercantile buildings. For educational and industrial building the following minimum requirements shall apply :-
(a) Educational building - Ceiling height 3.6 meters for all regions.
(b) Industrial building - Ceiling height 3.6 Meters but if air-conditioned, 3 meters (Factory Act, 1948 and rules made thereunder shall govern such height where applicable).
(3) Size:
(a) The area of habitable room, where there is only one room, shall not be less than 9.5 square meters and the minimum width shall be 2.4 meters. Where there are two rooms, one of these shall not be less than 9.5 square meters and the other be not less than 7.5 square meters with a minimum width of 2.1 meters. In the case of hostels in educational institutions the minimum size of a habitable room for single person shall be 7.5 square meters.
(b) However, in the case of special housing schemes for Economically Weaker Section of Society, Low Income Group Housing, the norms for the size of the rooms shall be as provided in Appendix-J.
Rule 70-71
88
Kitchen.- (1) Height: The height of a kitchen measured from the surface of floor to the lowest point in the ceiling (bottom slab) shall not be less than 2.6 meters except for the portion to accommodate floor trap of the upper floor.
(2) Size : The area of a kitchen where separate dining area is provided shall not be less than 5.0 square meters with a minimum width of 1.8 meters. Where there is a separate store, the area of kitchen may be reduced to 4.5 square meters. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 square meters with a minimum width of 2.1 meters.
(2) Other Requirements,-
(a) Dimensions of septic tanks : Septic tanks shall have minimum width of 75 centimeters and minimum depth of one meter below the surface level and a minimum liquid capacity of one cubic meter. Length of tanks shall be 2 to 4 times the width;
(b) septic tanks may be constructed of brick work /stone masonry/ concrete or other suitable materials as approved by the Authority;
(c) under no circumstances should effluent from a septic tank be allowed into an open channel drain or body of water without adequate treatment;
(d) minimum nominal diameter of pipe used shall be 100 millimeters. Further at junctions of pipes in manholes, direction of flow from a branch connection should not make an angle exceeding 45 degrees with the direction of flow in the main pipe;
(e) the gradients of land drains, under-drainage as well as the bottom of dispersion trenches and soak ways should be between 1:300 and 1:400;
(f) every septic tank shall be provided with ventilating pipe of at least 50 millimeters diameter. The top of the pipe shall be provided with a suitable
Rule 80
93
case of mosquito proof wire mesh. The ventilating pipe shall extend to a height, which would cause no smell nuisance to any building in the area. Generally, the ventilating pipe may extend to a height of 2 meters when the septic tank is located at a distance of 15 meters from the nearest building and to a height of 2 meters above the top of the building when it is located closer than 15 meters;
(g) when the disposal of septic tank effluent is to seepage pit, the seepage pit may be of any suitable shape with the least cross-section dimension of 90 centimeters and not less than 100 centimeters in depth below the invert level of the inlet pipe. The pit may be lined with stone, brick or concrete blocks with dry open joints which should be backed with at least 7.5 centimeters of clean coarse aggregate. The lining above the inlet level should be finished with mortar. In the case of pits of large dimensions, the top portion may be narrowed to reduce the size of the reinforced cement concrete cover slabs. Where no lining is used, specially near trees, the entire pit should be filled with loose stones. A masonry ring may be constructed at the top of the pit to prevent damage by flooding of the pit by surface run off. The inlet pipe may be taken down to a depth of 90 centimeters from the top as an anti-mosquito measures; and
(h) when the disposal of septic tank effluent is to a dispersion trench, the dispersion trench shall be 50 to 100 centimeters deep and 30 to 100 centimeters wide excavated to gradient and shall be provided with 10 to 25 centimeters of washed gravel or crushed stone. Open joints placed inside the trench shall be made of unglazed earthenware pipes clay or concretes and shall have minimum internal diameter of 75 to 100 millimeters. Each dispersion trench should not be longer than 30 meters and trenches should not be placed closer than 1.8 meters.
Projections.- (1) Projection into open spaces - Every minimum open space provided on the exterior side and every open space provided on the interior shall be kept free from any construction thereon and shall be open to the sky except as below :-
(a) Cornice, roof or weather shade not more than 0.75 meter wide;
(b) Sunshade over window/ventilators or other openings not more than 0.75 meters wide;
(c) Projected balcony at first or higher floors extending upto 1.20 meters with clearance of 1.5 meters from plot boundary provided that such projected balcony shall not be constructed as a continuous projection on any side of the building,
(2) Projections mentioned above in sub-rule (1)(c) may be permitted on the inner courtyard, if the size of such courtyard is more than 9 meters x 9 meters.
(3) Projecting rooms at alternate floors may be allowed :
Provided that such projection,-
(a) do not obstruct the air and light of the lower two floors;
(b) do not project into the MOS; and
(c) shall not be more than the height of the storey immediately below.
(4) Accessory Building - The following accessory buildings may be permitted in the open spaces :-
(a) In existing building, sanitary block of 2.4 meters in height subject to a maximum of 4 square meters in the rear open space at a distance of 1.5 meters from the rear boundary may be permitted.
(b) Private garages with an area not exceeding 25 square meters shall be permitted in the rear end of side open spaces.
(c) Pump room and watchman hut each up to 6.0 square meter.
(5) Sunshades over windows and ventilators - Projections of sunshades over windows or ventilators in existing built-up or congested areas when permitted by the Authority shall fulfill the following conditions, namely :-
Rule 59-60
82
(a) no sun-shade shall be permitted over the road or over any drain or over any portion outside the boundaries of the site below a height of 2.8 meters from the road level;
(b) sunshades provided above a height of 2.8 meters from the ground level shall be permitted to project up to a maximum width of 60 centimeters, if the road over which they project exceeds 9 meters in width; and
(c) no sunshade shall be permitted on roads less than 9 meters width or on roads having no footpath.
Limitation to open spaces.- (1) Safeguard against reduction of open spaces - No construction work on a building shall be allowed if such work operates to reduce an open space of any other adjoining building belonging to the same owner to an extent less than what is prescribed at the time of the proposed work or to reduce further such open space if it is already less than that prescribed.
(2) Additions or Extensions to a building- Additions or extensions of building shall be allowed provided that the open spaces for the additions or extensions would satisfy these rules after such additions or extensions are made.
Group housing.- Planning Norms for Group Housing shall be as below :-
(1) The minimum land or plot area, ground coverage, minimum soft area and such other planning norms for group housing shall be as published by the State Government in the official Gazette.
(2) The coverage and floor area ratio for various densities may be as provided in Table 7 unless otherwise provided in the development plan.
TABLE 7FLOOR AREA RATIO AND COVERAGE FOR GROUP HOUSING [See Rule 60(2)]
S.No.
Gross residential density Persons/Hectare
Maximum coverage in per cent.
Floor Area Ratio
(1)
(2)
(3)
(4)
1.
125
25
0.75
2.
250
30
1.25
3.
425
33
1.50
4.
500
35
1.75
5.
625
35
2.00
Rule 61
83
Note : The coverage shall be calculated on the basis of the whole area reserved for group housing after deducting :-
(i) the area of any highway or any road of width 18 mtrs. or more which falls within the area of Group Housing;
(ii) the area of school (excluding sites for Nursery Schools) and other community facilities within the Group Housing Area; and
(iii) the prescribed open space (playgrounds and tot lots of local nature shall be permitted in these open spaces).
Permission for high rise buildings challenged -- Except a bald allegation that density norms have not been followed, no violation of any statutory provision shown - - Substantial question of public interest not involved in the case -- PIL dismissed. Pradeep Hinduja Vs. State of M.P. and another, 2019 (2) MPLJ 668 = 2018 Supreme 942 (MP).
(3) Other requirements : Every room to be used as kitchen shall have,-
(a) unless separately provided in a pantry, means for the washing of kitchen utensils which shall lead directly or through a sink to a grated and trapped connection to the waste pipe;
(b) an impermeable floor;
(c) a flue, if necessary; and
(d) a window or ventilator or opening of size not less than as specified in note 3 of sub-rule (3) of rule 82.
Bathroom and Water Closets.- (1) Height : The height of a bathroom or water closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.2 meters.
(2) Size : (a) The size of a bathroom shall not be less than 1.5 square meters. The minimum floor area of water closet shall be 1.1 square Meters with a minimum width of 0.9 meter. If bath and water closet are combined, its floor area shall not be less than 2.4 square Meters with a minimum width of 1.2 meters. The area of Water Closet with wash basin shall not be less than 1.3 square meters;
(b) the minimum sizes of bathrooms/water closets shall be as follows:
(i) Independent water closet 1.1 meter X 0.9 meter.
(ii) Independent bathroom 1.3 meter X 1.1 meter.
(iii) combined bathroom and closet - 2.0 square meters with, minimum width of 1.1 meters.
(iv) Water closet with wash basin - 1.3 square meters.
(3) Other requirements : Every bathroom or water closet shall,-
(a) be so situated that at least one of its walls shall open to external or internal open space;
(b) not be directly over or under any room other than another water closet, washing place, bath or terrace, unless it has a water tight floor;
(c) have the platform or seat made of watertight non-absorbent material;
Rule 72-73
89
(d) be enclosed by wall or partitions and the surface of every such wall or partitions shall be finished with a smooth impervious material to a height of not less than I meter above the floor of such a room;
(e) be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards verandah or any other room; and
(f) have a window or ventilator, opening to a shaft or open space, of area not less than 3 square Meters with side not less than 0.3 meter.
(4) No room containing water-closet shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
Ledge or Tand/Loft.- (1) Height : It shall have a minimum head-room of 1.5 meters.
(2) Size : A ledge or "tand" in a habitable room shall not cover more than 25 per cent. of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
(3) Loft : A loft, if provided, on a kitchen shall not exceed 25 per cent. of the area of kitchen and shall leave minimum height of 2.2 meters under the loft. On bathroom, water-closet and corridor, the loft may cover as much area as would allow a person to keep article there with reasonable space for body movement.
Mezzanine (Entresol) Floor.- (1) Height : It shall have a minimum height of 2.2 meters.
(2) Size : The size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5 square meters. The aggregate area of such mezzanine floor in a building shall in no case exceed 1/3 of the plinth area of the room in which it is provided.
(3) Other requirements : A mezzanine floor may be permitted over a room or a compartment:
Provided that,-
(a) it conforms to the standards of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.5 square meters or more;
(b) it is so constructed as not to interfere, under any circumstances, with the ventilation of the space over and under it;
(c) such mezzanine floor is not sub-divided into smaller compartments;
(d) such mezzanine floor or any part of it shall not be used as a kitchen; and
(e) a mezzanine floor shall be kept open on at least one side.
Rule 74-76
90
Store room.- (1) Height : The height of a store room shall not be less than 2.2 meters.
(2) Size : The size of a store room, where provided in a residential building shall not be less than 3 square meters.
Garage.- (1) Height : The height of a garage shall not be less than 2.2 meters.
(2) Size : The size of garage shall not be less than as below :-
(a) Private Garage-2.5 meters X 5.0 meters.
(b) Public Garage- Based on the number of vehicles parked etc., (Refer rule 84 parking space).
Basement.- (1) Basement shall not be used for habitable purpose except in case mentioned in sub-rule 2 (c).
(2) The construction of the basement may be allowed in all the land uses subject to the following conditions, namely :-
(a) basement shall not extend into the prescribed MOS :
Provided that where minimum MOS are more than 12 meters in front or more than 7.5 meters on all other sides, in that case basement may be allowed leaving 12 meters distance in front and 7.5 meters on other sides;
(b) the plinth level of the building in which the basement is built shall not be more than 0.45 meters above the surrounding ground; and
(c) in certain cases, depending on the topography of the site the part of the building below the ground or reference level could also be called the basement and if such part is habitable, then it may be used accordingly and shall be added in the calculation of FAR.
(3) Basement can be used for only the following purposes, namely :-
(a) storage of noncombustible articles;
(b) strong rooms, bank cellars, radiation room (only for medical treatment and research);
(c) air-conditioning equipments and other machines used for services and utilities of the building;
(d) parking spaces;
(e) commercial activity only on the first basement level:
Provided that :
(i) the land use of the premises / plot is commercial;
(ii) the plot area is not less than 1.0 hectare; and
(iii) the building is detached.
Rule 77
91
Note : The basement area permitted for commercial use in sub-rule 3(e) shall be taken into account for the purpose of calculating FAR.
(4) The basement shall have following requirement, namely :-
(a) basement in every part shall have a clear height of at least 2.4 meters as measured from the floor to the underside of the beam. In case of clause 3(e) above, the minimum clear height as calculated above shall be 3.6 meters;
(b) adequate ventilation shall be provided for the basement, the ventilation requirements shall be the same as required by the particular occupancy according to these rules. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air. conditioning systems or the like;
(c) the maximum height of the ceiling of any basement shall be 0.45 meter above the surrounding ground level in such a fashion that vehicular movement in the MOS or around the buildings are not obstructed;
(d) adequate arrangements shall be made to prevent surface drainage from entering into the basement;
(e) the walls and floors of the basement shall be watertight and be so designed that the effect of the surrounding soil and moisture are taken into account in design and adequate damp proofing treatment done;
(f) the access to the basement shall be separate from the main entrance and in addition another staircase/ramp shall be provided for access to and exit from various floors of the basement. Where the staircase/ramp is continuous the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors; and
(g) open ramps as means of access to the basement may be permitted in such a manner that they do not obstruct the MOS in any manner.
(5) A maximum of three levels may be allowed in the construction of multi- level basements. Such multi-level basement may be allowed only if,-
(a) The minimum frontage of the plot is 21 meters and the minimum average depth 30 Meters and the plots abuts a road of width 18 meters or more; and
(b) the building is detached.
(6) If the built form below the ground or reference level is used as habitable accommodation because of the existing topography such area may be permitted as habitable area and shall be counted in the Floor Area Ratio.
Parapet.- Parapet walls and handrails provided on the edges of roofs terraces, balcony, corridors/ lobbies/ foyers or verandah shall not be less than 1.05 meters in height from the finished floor level.
Rule 78-79
92
Boundary Wall.- The requirements of boundary wall are given below:-
(a) The maximum height of the compound wall shall be 1.5 meters above the center line of the front street unless the Authority permits a higher wall.
(b) The rear and side compound walls shall not have a height more than 3 meters above the central line of the service road in case it exists otherwise it shall be not more than 2 meters. It shall be measured above the central line of the front street. In case of a corner plot the height of the boundary wall abutting on the side road shall also not be more than 1.5 meters.
(c) the provisions of (a) and (b) are not applicable to boundary walls of jails, electric sub-stations, transformer stations, institutional buildings, like sanatoria, hospitals, industrial buildings like work-shops, factories and educational buildings like schools, colleges, including the hostels and other uses of public utility undertaking, where height as required, may be permitted by the Authority.
Septic Tanks - Where a septic tank is used for sewage disposal, the location, design and construction of the septic tank shall conform to the following requirements:-
(1) Location of Septic Tanks and Sub-Surface absorption systems - A subsoil dispersion system shall not be located within 18 meters from any source of drinking water. It shall also be as removed from the nearest habitable building as economically feasible but not within 2 meters thereof so that there is no damage to the structures.
Staircase.- (1) The minimum clear width and maximum riser of staircases for buildings shall be as given in sub-rule (2) to (4).
(2) Minimum Width : The minimum width of staircase shall be as follows :-
(iii) Assembly buildings like auditorium, theatres and cinemas - 1.5 meters
(iv) Educational buildings :-
(a) up to 24 m. in height - 1.5 meters
(b) more than 24 m. in height - 2.0 meters
(v) Institutional buildings :-
(a) up to 10 beds - 1.5 meters
(b) more than 10 beds - 2.0 meters
(vi) All other buildings - 1.5 meters
Rule 81-82
94
(3) The landing width shall be a minimum of twice the tread plus 25 centimeters.
(4) Minimum Tread : The minimum width of tread without nosing shall be 25 centimeters for residential buildings. The minimum width of tread for other buildings shall be 30 centimeter.
(5) Maximum Riser : The maximum height of risers shall be 17 centimeters for residential buildings and 15 centimeters for other buildings and these shall be limited to 15 numbers per flight.
(6) Head Room : The minimum head-room in a passage under the landing of a staircase shall be 2.2 meters. The minimum clear head-room in any staircase shall be 2.2 meters.
Roofs.- (1) The roof of a building shall be so constructed or framed as to permit effective drainage of the rain water therefrom by means of sufficient rain- water pipes of adequate size, wherever required, so arranged, jointed and fixed as to ensure that the rain-water is carried away from the building without causing dampness in any part of the walls or foundations of the building or those of an adjacent building.
(2) The Authority may require rain-water pipes to be connected to a drain or sewer or a covered channel beneath the public footpath or in any other approved manner.
(3) Rain-water pipes shall be affixed to the outside of the external walls of the building or in recesses or chases cut or formed in such external walls or in such other manner as may be approved by the Authority.
(4) Rain/Roof water harvesting method shall have to be provided on all type of buildings having plot size more than 140 Square meter as per the options mentioned in APPENDIX- H-1, H-2 and H-3.
Construction of commercial complex -- Leaving space of 4.5 meter as off-street parking and 4.5 meter as open space, these are two different requirements which are to be fulfilled and cannot be clubbed together. Satish Nayak Vs. State of M.P. and others, 2018 (2) RN 1 (HC) = 2018 Supreme 292 (MP).