Every semi-detached and detached building shall have a permanently open airspace on sides, forming integral part of the site as below :-
(i) For detached buildings there shall be minimum side open spaces of 3 meters on both the sides :
Provided that for detached residential building up to 7 meters in height on plots with a frontage less than 12 meters, one of the sides open space may be reduced to 1.5 meters.
(ii) For semi-detached building there shall be a minimum side open space of 3.0 meters on one side. For Semi-detached building up to 10 meters in height on plots with a frontage up to 10 meters, the side open space may be reduced to 2.5 meters.
(iii) For row-type buildings, no side open space is required.
(4) Notwithstanding anything contained in sub-rule (2) and (3) garage may be permitted at rear end of the side open space.
(5) Open space for building of more than 12.5 meters height - For building of height above 12.5 meters the open spaces around building shall be as given in Table 4 and 5 of Rule 42.
(6) Interior open spaces for all buildings,-
Rule 56
79
(a) Inner Courtyard,-
(i) Every room (except bath, water closet and store room) that does not abut on either the front, rear or side open spaces shall abut on an inner courtyard, having minimum side of 3 meters.
(ii) Further the inner courtyard shall have a minimum area, throughout its height, of not less than the square of one-fifth the height of the highest wall abutting the courtyard :
Provided that when any room (excluding staircase bay, bathroom and water closet) is dependent for its light and ventilation on an inner courtyard, its dimension shall be such as is required for each wing of the building.
(iii) Where only water closet and bath room are abutting on the interior courtyard, the size of the interior courtyard shall be in line with the provision for ventilation shaft as given in clause (b).
(b) Ventilation Shaft - For ventilating the spaces for water closet and bath room in all types and height of buildings, if not opening on the front or side or rear or interior open spaces, shall open on to the ventilation shaft, the size of which shall not be less than the values given below :-
| Height of buildings | Size of ventilation shaft in | Minimum size of a side of |
|---|---|---|
| in meters | square meters | shaft in meters |
| (1) | (2) | (3) |
| Up to 10 | 1.2 | 0.9 |
| 12.5 | 2.8 | 1.2 |
| 18 | 4.0 | 1.5 |
| 24 | 5.4 | 1.8 |
| 30 | 8.0 | 2.4 |
| above 30 | 9.0 | 3.0 |
Note 1: For buildings above 30 meters mechanical ventilation system, shall be installed besides the provision of minimum ventilation shaft.
Note 2: For fully air-conditioned residential buildings the ventilation shaft need not be insisted:
Provided that the air-conditioning system is designed to work in an un-interrupted manner which means that there is an alternate source of power supply.
(c) Outer Courtyard- The minimum width of outer courtyard (distinguished from its depth) shall be 2.4 meters. If the width of the outer courtyard is less than 2.4 meters, then it shall be treated as a notch and the provisions of outer courtyard shall not apply.