Fire Protection Requirements for Buildings in Zone-I Category
| Sl. No | Measures | Group-A: Residential A-3, A-4, A-5, A-6 (see Note 3) | Group-B: Educationa l B-1, B-2 (see Note 3 and 23) | Group-C: Institutional al C-1, C-2, C-3 (see Note 3 and 23) | ||||||||
| I | II | III | IV | V | VI | VII | VIII | VII | VIII | IX | ||
| 1 | Access | P | P | P | P | P | P | P | P | P | P | P |
| 2 | Means of Escape | P | P | P | P | P | P | P | P | P | P | P |
| 3 | Compartmentation | P | P | P | P | P | P | P | P | P | P | P |
| 4 | Refuge Area | X | X | X | P | P | P | X | P | X | P | P |
| 5 | Emergency Lights | P | P | P | P | P | P | P | P | P | P | P |
| 6 | Exit Signs | P | P | P | P | P | P | P | P | P | P | P |
| 7 | Manually Operated Electronic Fire Alarm System (MOEFA) with Talk Back and PA system (see Note 1) | p | p | p | p | P | P | P | P | P | P | P |
| 8 | Fire Extinguishers | P | P | P | P | P | P | P | P | P | P | P |
| 9 | First Aid Hose Reel | P | P | P | P | P | P | P | P | P | P | P |
| 10 | Yard Hydrant | X | X | P | P | P | P | X | P | P | P | P |
| 11 | Down Comer | P | X | X | X | X | X | P | X | X | X | X |
| 12 | Wet Riser | X | P | P | P | P | P | X | P | P | P | P |
| 13 | Automatic Fire Detection and Alarm System (see Note2) | X | X | X | P | P | P | X | X | P | P | P |
| 14 | Automatic Sprinkler System | S | S | FS | FS | FS | FS | S | S | FS | FS | FS |
| 15 | Under Ground Tank | X | P4 | P5 | P6 | P5 | P6 | X | P7 | P5 | P6 | P6 |
| 16 | Over Head Tank | P8 | P9 | P10 | P10 | P11 | P11 | P12 | P13 | P11 | P11 | P11 |
| 17 | Fire Pumps Near UGT (with minimum pressure of 3.5Kg/cm2 at remotest location) | X | P15 | P16 | P17 | P16 | P16 | X | P19 | P15 | P16 | P16 |
| 18 | Booster Pumps at the Terrace Tank level with minimum pressure of 3.5 kg/cm2 | P14 | X | X | X | X | X | P14 | X | X | X | X |
| 19 | Auto D.G. Set | P | P | P | P | P | P | P | P | P | P | P |
| 20 | MCB/ELCB | P | P | P | P | P | P | P | P | P | P | P |
| 21 | Hose Boxes | P | P | P | P | P | P | P | P | P | P | P |
| 22 | Fireman's Grounding Switch | P | P | P | P | P | P | P | P | P | P | P |
Fire Protection Requirements for Buildings in Zone-I Category
| Sl. No | Measures | Group-D: Assembly D-1 to D-6 (see Note 22 and23) | Group-D: Assembly D-1 to D-6 (see Note 22 and23) | Group-D: Assembly D-1 to D-6 (see Note 22 and23) | Group-D: Assembly D-1 to D-6 (see Note 22 and23) | Group-E: Business E-1 (see Note 22) | Group-E: Business E-1 (see Note 22) | Group-E: Business E-1 (see Note 22) | Group-E: Business E-1 (see Note 22) | Group-F: Mercantile F-1, F-2 and F-3 (see Note 3 and 23) | Group-F: Mercantile F-1, F-2 and F-3 (see Note 3 and 23) | Group-F: Mercantile F-1, F-2 and F-3 (see Note 3 and 23) |
| Sl. No | Measures | X | VII | VIII | XI | X | VII | VIII | VI | VII | VIII | XII |
| 1 | Access | P | P | P | P | P | P | P | P | P | P | P |
| 2 | Means of Escape | P | P | P | P | P | P | P | P | P | P | P |
| 3 | Compartmentation | P | P | P | P | P | P | P | P | P | P | P |
| 4 | Refuge Area | X | X | P | P | X | X | P | P | X | P | P |
| 5 | Emergency Lights | P | P | P | P | P | P | P | P | P | P | P |
| 6 | Exit Signs | P | P | P | P | P | P | P | P | P | P | P |
| 7 | Manually Operated Electronic Fire Alarm System (MOEFA) with Talk Back and PA system (see Note 1) | P1 | P | P | P | P | P | P | P | P | P | P |
| 8 | Fire Extinguishers | P | P | P | P | P | P | P | P | P | P | P |
| Sl. No | Measures | Group-D: Assembly D-1 to D-6 (see Note 22 and23) |