As provided in Clause 5.1.9 and 6.4.5 of these Building Bye-Laws. 12.10.1 Requirements
(1) The access to the basement shall be either from the main or alternate staircase providing access and exit from higher floors. Where the staircase is continuing, the same shall be enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of the (4).
(2) In case of basement for office, sufficient number of exit ways and access ways shall be provided with a travel distance not more than 15.0m. The travel distance in case of deadend shall be 7.5m.
(3) The basement shall be partitioned and in no case compartment shall be more than 500Sq.m and less than 50Sq.m area except parking. Each compartment shall have ventilation standards as laid down in Bye-Laws separately and independently. The partition shall be made in consultation with Chief Fire Officer.
(4) The first basement (fully below ground level) can be used or services/parking/other permissible services. Lower basements, if provided, shall exclusively be used for the uses permitted in the Zonal Regulations only.
(5) Each basement shall be separately ventilated. Vents with cross-sectional area (aggregate) not less than 2.5 percent of the floor area spread evenly round the perimeter of the basement shall be provided in the form of grills or breakable starboard lights or pavement lights or by way of shafts. Alternatively, a system of air inlets shall be provided at basement floor level and smoke outlets at basement ceiling level. Inlets and extracts may be terminated at ground level with starboard or pavement lights as before. But ducts to convey fresh air to the basement floor level have to be laid. Starboard and pavement lights shall be in positions easily accessible to the firemen and clearly marked ‘SMOKE OUTLET’ or ‘AIR INLET’ with an indication of area served at or near the opening.
(6) The staircase of basement shall be of enclosed type having fire resistance of not less than two hours and shall be situated at the periphery of the basement to be entered at ground level only from the open air and in such positions that smoke from any fire in the basement shall not obstruct any exit serving the ground and upper stories of the building and shall communicate with basement through a lobby provided with fire resisting self-closing door of one hour rating. In case of basement being used as car parking only, the travel distance shall be 45m.
(7) In multi-storeyed basements, intake duct may serve all basements levels, but each basement and basement compartment shall have separate smoke outlet duct or ducts. Mechanical extractors for smoke venting system from lower basement levels shall also be provided. The system shall be of such design as to operate on actuation of smoke, heat sensitive detectors/sprinklers, if installed, and shall have a considerably superior performance compared to the standard units. It shall also have an arrangement to start it manually.
(8) Mechanical extractors shall have an internal locking arrangement so that extractors shall continue to operate and supply fans shall stop automatically with the actuation of fire detectors. Mechanical extractors shall be designed to permit 30 air changes per hour in
case of fire or distress call. However, for normal operation, only 30 air changes or any other convenient factor can be maintained.
(9) Mechanical extractors shall have an alternate source of power supply.
(10) Ventilating ducts shall be integrated with the structure and made out of brick masonry or RCC as far as possible and when this duct crosses the transformer area of electrical switchboard, fire dampers shall be provided.
(11) Kitchens working on gas fuel shall not be permitted in basement/sub-basement.
(12) If cut-outs are provided from basement to the upper floors or to the atmosphere, all side cut-out openings in the basements shall be protected by sprinkler headset closed spacing so as to form a water curtain in the event of a fire.
(13) Dewatering pump shall be provided in all bases.