-61~

| N-II | 9.10 (30 ft.) | 2.5 | Nil | S+5 | 18 | the parking floors or provision for parking shall be used for any other purposes. Mezzanine floors or any floor partition shall be computed under FAR and counted as a floor. |
| N-III | 12.20 (40 ft.) | 2.5 | 2.0 | Maximum Height 24 meter | ||
| N-IV | 18.30 (60 ft.) | 2.5 | 2.5 | No restriction on height and number of floors however it may be regulated by the master plan/development plan/zonal plan | ||
| N-V | 24.40 (80 ft.) | 3.00 | 2.5 | |||
| N-VI | 27.40 (90 ft.) | 3.25 | 3.0 | |||
| N-VII | 30.50 (100 ft.) | 3.50 | 3.5 | |||
(2) While sanctioning the plans on building with a road width of 12 feet and 16 feet the Authority shall ensure that enough parking spaces for vehicles have been made within the building and that the vehicles shall not parked on the road. Provisions related to length of the road in Table 6 shall be adhered to.
(3) Additional FAR up to 10% upto a maximum of 0.25 shall be allowed for dwelling units meant exclusively for LIG/EWS in a group housing scheme.
(4) In case of Educational, Institutional and Assembly building the maximum permissible FAR shall be 1.50 for plots up to 1000 sq. m. and 1.75 for plots above 1000 sq. m.
(5) In case of transport related activities such as; railway yards, railway station, bus stands, bus shelters, transport depot, airport, special warehousing, cargo terminals etc. the maximum permissible FAR shall be 1.50.
(6) In case of Industrial buildings the maximum FAR shall be 0.5 for polluting and hazardous industries. In case of non-polluting and household industries the maximum FAR shall be 1.5.
(7) The FAR and Height of the building may also be regulated by the master plan/development plan or the zonal plan.
(8) In case the plot is affected by a road widening and the owner of the plot voluntarily surrenders the affected portion of his land to the Authority without any claim of compensation or through a TDR (Transferable Development Right) scheme implemented by the Government the owner shall be entitled to build on the remaining plot an area, calculated on the basis of the FAR as applied to the total area prior to such surrender. Provided that the surrender of the land shall be effected by a deed of transfer to be executed by the owner in favour of the Authority for widening of road.
(9) Exclusive multistory parking blocks can be provided within the required setback area without reducing the driveway for the fire tender to the extent of minimum 6 meters. This will not be included in the calculation of FAR.
(10) FAR shall not include
A. Basements or cellars and space under a building constructed on stilts and used only as a parking space, and air conditioning plant room used as accessory to the principal use;
B. Stilt Parking
Bihar Building Bye-Laws
[Signature]

C. Exclusive Multi Storey Parking made only for the purpose of parking vehicles and not put to any other use.
D. Electric cabin or substation, watchman booth of maximum size of 3sq.m. with minimum width or diameter of 1.732 m., pump house, garbage shaft, space required for location of fire hydrants, electric fittings and water tank, society room of maximum 12 sq.mtr.
E. Projections and accessories buildings as specifically exempted from the open space/setback requirement.
F. Staircase room and lift rooms above the topmost storey, architectural features, and chimneys and elevated tanks of dimensions as permissible under the NBC; the area of the lift shaft shall be taken only on one floor.
G. 50% of the area of projected balcony as per bye laws 45(4) shall not include.
(11) Additional FAR may be allowed for Government Buildings/ Government Projects with the prior approval of the Government.
- Height of a building.-(1) The height of the building shall be governed by the limitations of Floor Area Ratio, open space (setbacks), and the width of the street facing the plot described as detailed below:
A. The maximum height of a building shall in no case exceed (1.5 times X the width of the road on which the plot abuts) + the front setback. It shall be applicable only in case of unused permissible FAR for plots abutting on road of average existing width not less than 9.10 m wide.
B. If a building abuts on two or more streets of different widths, the building shall be deemed to face upon the street that has the greater width and the height of the building shall be regulated by the width of the street.
Provided that the roads on the other sides shall also conform to provisions made under bye law 33.
(2) Notwithstanding anything contained in sub-bye law (1) the height restrictions with respect to approach Funnels and Transitional area of Airport as detailed in Table -17 and 18 shall be adhered to. Any height restrictions imposed by the Airport Authorities shall be adhered to.
(3) Notwithstanding anything contained in the Tables under sub-bye law(1), no Radio Aerial, T.V. Antenna, Cell phone tower or such similar type of installations exceeding 52 metres in height shall be erected without prior permission of the concerned Civil Aviation Authority/ Airport Authority.
(4) No building structure or installation exceeding the height indicated in the said Tables shall be permitted unless the applicant produces a 'No-Objection Certificate' from the Airport Authority.
Table- 17: Height restriction with respect to approach funnels
| Distance from nearest runway end (in metres) | Maximum Permissible height above the elevation of the nearest runway end |
|---|
A###
so12 - so24/2 - 14
b q
Bihar Building Bye-Laws
-63-
| Up to 360 | 0 |
|---|---|
| 361 to 510 | 6 |
| 511 to 660 | 9 |
| 661 to 810 | 12 |
| 811 to 960 | 15 |
| 961 to 1110 | 18 |
| 1111 to 1260 | 21 |
| 1261 to 1410 | 24 |
| 1411 to 1560 | 27 |
| More than 1560 | 30 |
| Distance of the Inner Boundary of the Transitional Area (Outer Boundary of the Air Port) [Metres] | Maximum Permissible height above the elevation of the airport reference point [metres] |
|---|---|
| Up to 21 | 0 |
| 22 to 42 | 3 |
| 43 to 63 | 6 |
| 64 to 84 | 9 |
| 85 to 105 | 12 |
| 106 to 126 | 15 |
| 127 to 147 | 18 |
| 148 to 168 | 21 |
| 169 to 189 | 24 |
| 190 to 210 | 27 |
| More than 210 M | 30 |
- Off Street Parking Space.-(1) In all buildings including Apartment buildings/ Group Housing, Hotels, Restaurants and Lodges, business buildings, commercial buildings, Institutional buildings like hospitals, Educational buildings like schools and colleges, multi-storied buildings/complexes etc. and all other non-residential activities provision shall be made for parking spaces as per the requirements mentioned in Table 19.
(2) The parking spaces may be provided in (for all schemes) A. Basements or cellars B. on stilt floor C. open parking area D. exclusive multi-level parking or E. Roof top parking in case of commercial/IT/ITES and corporate building F. A combination of any or all of the above. Any provision made for parking shall not be included in the FAR calculation.
Table 19: Parking space for different category of occupancies
Ing Bye-Laws
Bye Laoa/12/4
Bye Laoa/12/4
-64-
| SI.No. | Category of building/ activity | Parking area to be provided as percentage of total built up area |
|---|---|---|
| (1) | (2) | (3) |
| 1 | Shopping malls, Shopping malls with Multiplexes/ Cineplexes, Cinemas, Retail shopping centre and marriage halls and banquet halls | 35 |
| 2 | IT / ITES complexes, Hotels, Restaurants, Lodges, Nursing Homes, Hospitals, Institutional and other commercial buildings, Assembly buildings, offices, and Industrial buildings and High-rise buildings and complexes. | 30 |
| 3 | Residential Building, Residential apartment buildings, Group Housing, Clinics and small offices upto 50 sqm. | 25 |
(3) Off-street parking spaces shall be provided with adequate vehicular access to a street and the area of drives, aisles and such other provisions required for adequate maneuvering of vehicles.
(4) If the total off-street parking space required under these bye laws is provided by a group of property owners at a place for their mutual benefit, such parking spaces may be construed as meeting the off-street parking requirement, however, subject to the approval of the Authority. The Authority may also decide to develop such parking spaces and charge property owners to bear proportionate cost.
(5) Garage with locking facilities shall be included in the calculation of floor space for determining the requirement of parking space, unless this is provided in the basement of a building or under a building constructed on stilts with no external walls.
(6) The parking spaces to be provided shall be in addition to the open spaces (setback) required around a building under these bye laws.
(7) Misuse of the area specified for parking of vehicles for any other use shall be summarily removed / demolished by the Authority.
(8) For parking spaces in basements and upper storey of parking floors, at least two ramps of minimum 3.6 m width or one ramp of minimum 5.4 m width and in maximum 1:10 slope shall be provided. Such ramps may be permitted in the side and rear setbacks after leaving 3.60 meter space for movement of fire-fighting vehicles. Access to these may also be accomplished through provisions of mechanical lifts. The slab over which the fire tender shall move shall be cable of taking the load of fire engine, fire vehicle of atleast 45 tonnes.
(9) Up to 10% of cellar may be utilized for utilities and non-habitation purpose like A/C plant room, Generator room, Electrical installations, laundry etc.
[Illegible Handwriting]
for L = (2)/(472) · 14 Ahm. L Q
-65-
Bihar Building Bye-Laws
(10) At least 15% of the parking space in group housing, apartment buildings shall be earmarked for visitors. Such parking space shall be indicated by painting "Visitor's Parking" on the floor. The Visitors parking facility shall be open to all visitors and shall not be settled with any occupant.
(11) All buildings with a height of 15 m and above will have parking space earmarked for ambulance, fire tender and physically challenged persons. Such spaces shall be clearly indicated by painting on the floor the purpose for which the parking space is reserved.
(12) Apart from use of Basement for Services/Parking/ Storage, it may be used for other activities like library, Study Room, Games Room and Laundry only in case of Residential and Institutional Buildings.
- Requirement of Parts of Building.-The various parts of the buildings shall have the following minimum specifications.
(i) Plinth
(a) Main Buildings: The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 450 mm from the surrounding ground level.
(b) Interior Courtyards and Covered Parking: Every interior courtyard shall be raised at least 150 mm above the determining ground level and shall be satisfactorily drained.