n = number of separate suspension ropes under load,
k - roping factor, that is 1 for 1: 1, 2 for 2:1 roping and
w = maximum static load imposed on all car ropes with the car and its rated load at any position in the Lift well in the same units as F
(3) The car and counterweight ends of the suspension ropes shall be fastened by spliced return loops or clipped return loops or individual tapered babbitted sockets. Loops shall not hold directly on their fixings, but shall be lined with proper thimble eyes or equal protection. In all cases the fastenings shall be capable of sustaining a load not less than 80 percent of the minimum breaking strength of the suspension ropes;
(4) A data plate indicating the following shall be fixed on the cross head of the car frame:
(i) Diameter of rope
(ii) Number of ropes, and
(iii) Manufacturer's rated breaking strength of rope in kilograms.
(5) All ropes anchored to a winding drum shall have not less than one complete and one half turns of the ropes on the winding dram when the Lift car or counter weight as reached the extreme limit of its over travel.
(6) Every Lift car or counter weight rope shall be free from joints.
(7) Rope compensation shall be used for any travel but it shall be necessary for travels over 30 meters.
(8) The winding drum and the Lift car and counterweight suspension ropes shall be properly secured by clamps on the inside of the drum.
(9) Means shall be provided for adjusting the lengths of the ropes to equalize the load on the individual suspension ropes.
ent any porting
ension
he Lift
25
PART I]
red. It
osition
pes on
:lamps
(10) The material, quality, construction, suspension ropes and the fixing of ropes shall, as far as possible, conform to Indian standards and methods pertaining to the same.
(11) Tensioning devices for compensation ropes, governor ropes and the like shall be protected against damage due to falling objects.
(12) Each suspension rope shall be separately and independently fixed to the car and to the counterweight. The simple suspension of the Lift car or the counter weight by means of a sheave or the like shall count as one suspension only.
(13) The minimum diameter of ropes for car and counterweight of passenger & goods Lifts shall be 8mm.
Controllers and operating devices.—(1) A manually operated mains disconnecting switch shall be installed in the main circuit cables of electric Lift machines or motor generator sets. This switch shall be placed close to and visible from the machine or motor generator set controls.
(2) When there are more than one Lift machine in machine room, each machine shall have a separate disconnecting switch. These switches shall be numbered to correspond to the number of the driving machine which they control and they shall be conveniently situated with respect to the driving machine.
(3) When any type of contact is used on the controller switches, for disconnecting the main circuit, at least two independent current breaks shall be incorporated in the design. In the event of an earth fault with any door open, the Lift shall not work.
(4) Operation of a spring or springs in tension or the completion of another electric circuit shall not depend on to break the circuit to stop the Lift at terminal landings.
(5) The interruption of the electrical circuit shall stop and prevent the movement of the car.
(6) Each Lift machine operated by a poly-phase A. C. motor shall be protected against phase reversal or failure. This protection shall be extended to A. C. motor.
(7) All control circuits shall be independently protected by fuses or miniature circuit breaker.
(8) The voltage of any controller operating circuit shall not exceed 250 volts. The control circuit shall be suitably protected independent of the main circuit and it shall be so arranged that an earth fault or open circuit shall not create an unsafe condition.
(9) It shall not be possible to start the Lift car under normal operation unless every landing door and car door is in the closed position.
(10) Following requirements shall be complied with when the Lift is put in “inspection mode”:
(i) It shall not be possible to control the car from any other position;
(ii) The car will travel only at a speed of 25% of the rated speed subject to a maximum of 1.0 meter per second.
(iii) The car shall not move until all safety devices are in position.
(11) Every Lift having winding drum machine shall be provided with a switch or device of adequate capacity which shall automatically cut of electric supply and shall stop the machine in the event the Lifting ropes of the Lift car become slack either due to any obstruction of the Lift car in its travel in the descending direction or due to any other cause whatsoever;
(12) Emergency stop switches for short circuiting the landing door lock circuit shall be prohibited.
(13) An emergency stop switch, of manually opened and closed type, shall be provided on the top of every Lift car and in the Lift pit and shall be marked conspicuously.
(14) All Lift traveling at a speed of 1 meter per second and above shall be provided with floor leveling device.
THE KOLKATÀ GAZETTE, EXTRAORDINARY, NOVEMBER 11, 2022
[PART I]
(15) Signal bells or similar apparatus, which can be operated from any floor in connection with an indicator in the Lift car shall be provided on all Lift operated by Lift operators.
(16) The operation of the fire Lift in building having more than 30 meters height, shall be a simple toggle or two button switch situated in a glass box painted with red color adjacent to the Lift at entrance level on the ground floor. When the switch is ON, the landing call points shall become inoperative and car shall report to the ground floor and the same shall remain on car control only. When the switch is "OFF", the Lift shall return to normal working.
(17) Floor position indicator shall be provided in the Lift car as well as at every landing.
(18) Car top shall be provided with a suitable wire mesh guard to provide safety to persons working thereon for maintenance of Lift.
Terminal stopping and final limit switches.- (1) Every electric Lift shall be provided with upper and lower normal terminal limit switches arranged to stop the car automatically within the limits of top car clearance and bottom run by (over travel) from any speed attained in normal operation. Such limit switches shall act independently of the operating device, the ultimate or final limit switch and the buffers.
(2) Normal terminal limit switch shall be fitted in the Lift car or in the Lift well or in the machine room, and such switches shall be brought into operation by the movement of the Lift car.
(3) When terminal limit switches are situated in the machine room, they shall be mounted on and operated by stopping device mechanically connected to and driven by the Lift car without friction. An automatic safety switch shall be provided to stop the Machine in case of failure of tape, chain, rope or other similar device.
(4) Electric Lifts shall be provided with ultimate or final limit switches arranged to stop the car automatically within the top and bottom clearances independent of the normal operating device and the terminal limit switches. The switches and the oil buffer shall be so arranged that the opening of the switch and the engagement of the buffer shall be as nearly simultaneous as possible. When spring buffers are employed, the switch shall open before the buffers are engaged.
(5) Final limit switches shall act to prevent movement of the Lift car under power in both directions of travel and shall after operation, remain open until the car has been moved by a winding to a position within the limits of normal travel.
(6) Final limit switches shall act to prevent movement of the Lift car and shall be operated by the movement of the Lift car in the Lift well,
(7) Final limit switches shall not control the same switches on the controller as those controlled by the normal terminal limit switches unless two or more separate and independent switches are provided.
(8) All normal terminal stopping switches whether mounted on the Lift car or in the Lift well shall be of enclosed type and shall be securely mounted. The contacts of all terminal stopping devices shall be opened positively and mechanically by the movement of the Lift car.
Note:- In the case of electric Lift using floor controller or other similar devices for automatic stopping at the floor landing only one set of floor stopping contacts shall be necessary for each terminal landing provided these contacts and the means of operating them comply with the requirements for terminal stopping devices.
Electrical wiring and apparatus.—(1) The electric supply line and apparatus of the Lift shall be of sufficient ratings of power, insulation and estimated fault current and of sufficient mechanical strength for the duty which they may be required to perform, Over current protection for power and control circuits, shall be provided.
(2) Each Lift shall be capable of being isolated from the main supply by suitable locking arrangement.
(3) For banks of interconnected Lifts, a separate sub circuit is required for the common supervisory system, in order that any one car may be shut down without isolating the supervisory control of the remainder.
(4) Machine rooms enclosing Lift equipment shall be provided with adequate illumination controlled by a switch fixed adjacent to it's the entrance. At least one socket outlet, suitable for lamps or tools, shall be provided in this room.
[PART I
——
r in the
or two ground to the return
eon for
I lower
ice and idently
nd such
nted by safety
evice.
utically d limit
gement h shall
vel and mits of
ment of
normal
nclosed
itively
e floor
cts and
ficient which
d.
em, in
switch
ided in
PART I]
27
(5) The supply to the car light shall be from a separate circuit, and controlled by an independent switch located in the machine room. For multiple Lifts with a common machine room a separate supply shall be provided for each car. The car lighting shall be independent of the power supply mains.
(6) Three pin sockets with switch and a light point shall be provided on each floor. The power supply for this shall be controlled by a switch provided in the Lift well and accessible from the terminal floor entrance.
(7) When the alarm system is connected to a transformer or trickle charger, the supply shall be taken from the machine room lighting or when available, from the building fire alarm system.
(8) All electric supply lines and apparatus in connection with the Lift installation shall be so constructed, installed, protected and maintained so that there may be no danger to persons there from.
(9) A battery-operated telephone shall be provided in the Lift car and for the purpose, a cabinet shall be fitted (optional) in the car and wiring shall be provided from car to terminal box adjacent to the Lift well. Such telephone shall be receivable at the ground floor.
(10) All metal casings or metallic coverings containing or protecting any electric supply lines or apparatus shall be efficiently earthed.
(11) No bare conductor shall be used in any Lift car as may cause danger to persons.
(12) A danger notice in Hindi or English and Bengali with a sign of skull and bones shall be affixed on the (i) door of the machine room, (ii) Lift motor and (iii) Lift controller.
Testing.—(1) No new Lift shall be brought into use unless the Lift has been tested to determine whether its safety gear, brakes, terminal stopping devices buffers, over speed governor etc. operate satisfactorily.
(2) The person or firm responsible for the installation of a Lift shall certify in writing that the test carried out by him to determine the suitability of the Lift for normal and regular service, has been satisfactory and, if required by the Inspector of Lifts, such tests shall be carried out in the presence of and to satisfaction of the Inspector of Lifts.
(3) The Inspector of Lifts may also himself carry out such tests as he may think necessary for his satisfactory, to determine the suitability of the Lift for normal and regular use. Such tests shall be carried out in presence of the representative of the person or firm who is responsible for the installation of the Lift.
(4) For the test of safety gear, the test shall be carried out with contact load in the Lift car to determine whether it operates satisfactory. If the safety gear is of the gradual wedge-clamp or flexible guide-clamp type, the test shall be made to determine whether the safety gear will operate within the maximum and minimum stopping distances given in the table under Rule 36.
(5) The over speed test shall be made with ropes attached and all electrical apparatus operative except for the over speed contact or cut on the governor. For Lifts operating directly from alternating current the governor shall be tripped by hand at maximum speed obtainable.
Sundry precautions.- (1) Adequate precaution shall be taken to guard against any possibility of a Lift being operated by unauthorized persons. Precautions shall also be taken to prevent a Lift from being operated by any person when it is not intended for use.
(2) An authorized person shall be on duty in the premises where a Lift is installed during the whole period the Lift remains in actual use.
(3) No person shall remain in the pit while the Lift is working. Adequate precautions shall be taken to protect persons working in the pit from accidental contact with the counterweight.
(4) While a Lift is under examination or repairs, suitable steps shall be taken to ensure that the Lift is not operated inadvertently by any person in such a manner as may endanger the safety of persons working in the Lift.
(5) No such explosive or other inflammable material shall be carried in the Lift car as may endanger the safety of persons.
[PART I]
Relaxation of Rules to run Lift.- In the ease of Lifts operated by power other than electricity, an Inspector of Lifts may, by order in writing, relax the provision of these Rules to such extent as it may be necessary to run such Lift. Such Lifts must, however, comply with such instructions as may be issued in this behalf by the Inspector of Lifts with the approval of the State Government.
Authority to lodge complaint.- An Inspector of Lifts or any other person duly authorized by the State Government in this behalf may make a complaint to the Criminal Courts for an offence punishable under Section 14 & 15 of the Act.
Chapter IIIInstallation of Lifts
Lift wells. -(1) Every Lift well intended for the installation of the Lift or any equipment necessary for its maintenance shall be exclusively reserved for that purpose and shall not be used for any other purpose;
(2) The inner sides of a Lift well shall, so far as practicable, form a smooth, continuous flush surface devoid of projections or recesses. Where any projections extending inwards from the general surface of the enclosure at or near openings or landing cannot be rendered flush, then they shall be leveled on the underside to an angle of not less than 60 degree from the horizontal by means of metal plates, cement rendering, or other suitable fire resisting materials.
(3) Where there is more than one Lift in common well, a width of minimum allowance of 100 millimeters for separator beam shall be made.
(4) Where there is more than one Lift in common well, a suitable separator screen throughout the whole height of Lift well having adequate strength shall be fixed in the Lift well to protect the person working in the Lift well or in the Lift car, from accidental contact with counter weights and other Lift car at any state of their travel.
(5) No room, passage or thorough fare shall be provided under any Lift well except in case of the Lift having counter weight fitted with over speed governor safety device.
(6) Where a Lift car leveling device is operative with the Lift car gate opening such interior surfaces shall always form a smooth flush surface below each landing level for a depth to at least the depth of the car leveling zone plus distance through which the Lift car may travel of its own momentum when power is cut off.
(7) Sufficient space shall be provided between the guides for the car and the side walls of the Lift well enclosure to allow safe and easy access to the parts of the safety gear for their maintenance and repairs.
[PART I]
(8) Every Lift well, together with the whole of the equipment and apparatus contained therein, shall be rendered fire resisting to the greatest possible extent.
(9) A notice with the word "Lift" shall be placed on the outside of each landing door.
(10) (10) The Lift well shall conform to specifications laid down by Bureau of Indian Standards specification BIS-14665 (Part-1)-2000.
Lift wells enclosures. – (1) Except as provided in sub-rule (2) every Lift well shall be protected by a substantial fire resisting enclosure extending on all sides and fitted with gates or doors. The enclosure shall be so constructed that no person may fall down in the Lift well or come into contact with any moving part of the Lift when the gates of doors are shut.
(2) Where fire-resistance construction cannot be provided, the Lift well shall be enclosed to a height of not less than 1.83 meters or such greater height as may be recommended by the Chief Electrical Inspector.
(3) Where wire grill or similar construction is used, the mesh or opening shall not be greater than 3 centimeters and the Lift well enclosure shall be of sufficient strength to resist accidental impacts by users of the staircase or adjoining floors, and in the case of goods Lift, by movements of materials in the vicinity.
(4) Where the clearance between the inside of an open type Lift well enclosure and any moving or movable part of the Lift equipment or apparatus is less than 5 centimeters, the openings in the enclosure shall be further protected by netting of square mesh not greater than 13 millimeters and of wire not smaller than 1 millimeter or in a manner approved in writing by the Inspector of Lifts.
(5) The Lift well enclosure on the sides used for loading and unloading shall not be at a distance of more than 13 cms from edge of the Lift car platform.
(6) There shall be no opening in the Lift well enclosure permitting access to the Lift car by passing under the counterweight.
(7) In the construction of Lift well enclosure glass shall not be used. However condition may be relaxed in case of specially designed, well protected, fully transparent laminated type safety glass construction as may be permitted by the Chief Electrical Inspector. A certificate from the qualified structural engineer regarding the proper fixation in respect of such type of construction shall be submitted.
(8) Lift wells and wells for the counterweight, if located independently of the Lift well shall be adequately protected by means of suitable enclosure work which shall be extended on all sides from floor to ceiling.
(9) In all counter-weight wells located independently of the main Lift well, suitable access shall be provided for the inspection, maintenance and repairs to counter-weights, wire ropes and their anchorages, guides and guide supports.
(10) All such doors giving access to such counter-weight wells shall be provided with electromechanical locking devices.
(11) No counter weight shall be allowed to travel in any Lift well or part of any Lift well other than that to which it belongs.
(12) The Lift well enclosure on the sides facing any Lift car entrance shall so far as is practicable, be not more than 25 millimeters from the edge of the Lift car platform.
(13) The walls enclosing Lift well in the buildings having height more than 30 meters shall have fire resistance of not less than two hours. The Lift well shall have permanent vents immediately under the machine room not less than 0.2 square meter in clear area.
(14) The Lift well for fire Lift (a Lift to enable fire brigade personnel to get to the upper floors with the minimum delay and to be used exclusively by firemen in an emergency and directly accessible to every landing on every floor), in the building having more than 24 meters height shall be segregated from the other Lift wells by means of brick masonry or R.C.C. wall of a fire resistance of not less than two hours.
(15) Fire Lift in a building having more than 24 meters travel, shall work at such speed so as to reach the top floor from ground level within one minute.
27..
[PART I]
——
ndered
.
ication
stantial
tructed
e gates
not less
meters
aircase
ple part
further
limeter
han 13
der the
in case
nay be
ing the
quately
ling.
led for
es and
ocking
which
t more
nce of
om not
minimum
a every
ells by
p floor
PART I]
15
(16) Thickness of the Lift enclosure wall shall be of minimum 150 millimeters for R.C.C structure or 250 millimeters for brick construction.
(17) Capsule Lifts as well as glass Lifts shall not be allowed to be installed "open to sky". Whenever installed in house, following provisions shall apply.
(i) Lift well enclosure of this type of Lifts shall have partial covering on one side in which capsule Lift protruding structure moves. The area immediately beneath this side of the Lift enclosure shall be declared as no man area and shall be provided with adequate guarding.
(ii) In case of glass Lift, one side of the Lift enclosure shall have clear laminated safety glasses of minimum 8 millimeters thickness. The area beneath this side of the Lift enclosure shall be declared as no man area and shall be provided with adequate guarding.
Lift pit. - (1) A pit of adequate depth shall be provided for every Lift below the level of its lowest landing.
(2) The Lift pit shall be so constructed as to be capable of withstanding the impact of the Lift car with the rated load or the impact of the counter-weight when either is descending at rated speed or at governor tripping speed in case governor operated safety gear is used.
(3) The Lift pit shall be of adequate size, treated with water proofing compound, net cemented and shall be maintained in a dry and clean condition. The floor of the Lift pit shall be approximately level and where necessary provision shall be made for permanent drainage.
.(4) Where the pit depth exceed 2 meter, suitable access shall be provided by a ladder or any other suitable device and light point with a switch along with a car control switch at entrance level shall also be provided for facility of maintenance and repair work.
27Bottom and top car clearances. -
(1) Bottom Car Clearance – when the car rests on its fully compressed Buffer, there shall be vertical clearance of not less than 600mm between the Pit Floor and Buffer Striker or the lowest structural or Mechanical part, Equipment or Device installed. This clearance shall be available between the whole areas of the Platform except for –
(i) Guide Shoe or Rollers, Safety Jaw Blocks, Platform Aprons, Guides or other equipments located within 300mm. measured horizontally from the sides of the Car Platform, and
(ii) Compensating Sheaves -
Provided that in all the cases when the Car rests on it's fully compressed Buffer, there shall be a vertical clearance of not less than 50mm between any part of the Car and any obstruction of device mounted in the Pit.
(2) Top Car Clearance –
The vertical clearance between the Car crosshead and the nearest overhead obstruction within 500mm measured horizontally, to the nearest part of the crosshead when the Car Platform is level with the Top Landing shall not be less than 900 mm for the contract speed less than 1.5m/s and 1500 mm for the contract speed 1.5 m/s or above.
In case of oil or similar buffer used, Inspector of Lifts may permit such clearances as he may consider adequate for car & counterweight.
Landing doors. - (1) The landing doors of all Lifts other than goods Lift shall not be imperforate, where auto-rescue device is not provided and/or the Lift is used in any building of more than three floors above ground floor.
(2) All landing openings in Lift well enclosure shall be protected by doors which shall extend the full height and full width of the landing opening. The top track of a landing door shall not obstruct the entrance to the Lift car.
[PART I]
PART I
(3) The Distance between the Lift well side of the car door and the Lift well side of the landing door shall not exceed 13 centimeters; where the car door or the landing door consists of two or more panels, the 13 centimeters dimensions shall apply to the door panel nearest to the side edge. The distance between the car and the landing sills shall not exceed 30 millimeters.
(4) The opening for the landing doors shall be not wider than that of the width of Lift car. Minimum landing door opening width and height shall be 0.68 m and 2 m respectively.
(5) Landing doors and their tracks shall be capable of withstanding a thrust of 345 N applied normally at any point, excepting any vision panel, without causing permanent deformation and without the doors being sprung from their tracks.
(6) In the case of close type of landing doors and car doors, a vision panel, with maximum 225 millimeters x 125 millimeters in size is optional. Any projection on or recesses (including vision panel) in the sliding car doors shall be kept to a minimum in order to avoid finger trapping between sliding parts of the door and any fixed part of the structure.
(7) Hangers and tracks for doors together with their fixings shall be of adequate strength to withstand stresses specified in sub rule (5). Means shall be provided to prevent hangers for all landing sliding doors from jumping in the tracks or jamming and suitable stops shall be provided to prevent the hanger carriage from leaving the end of the track.
(8) The landing doors shall be securely fixed. The landing doors which are self closing shall be equipped with safety devices fitted on the Lift door to prevent persons while entering or leaving the Lift car.
(9) Swing doors may be used where hoist way width is not enough to accommodate sliding doors. The distance between swing door and Lift car door shall not exceed 7.5 centimeter upto a height of 600 millimeters from the bottom of the door.
(10) Entrance frame of the swing door shall be designed to support in place the panel with its hinges or pivots, door closer if attached to the frame and interlock. It shall withstand the forces referred to in Sub-Rule (5) and the forces resulting from the normal opening of the door or normal attempts to open it when locked in the closed position.
(11) All collapsible type landing doors of Lifts and for goods Lift used on industrial premises shall be of a closed picket type and no openings shall exceed 5.5 centimeters in width between the vertical members of the doors when it is fully extended.
(12) Automatic fire door or shutter which operates by means of a fusible link or otherwise due to the action of heat, shall not be allowed in any landing, opening or in the Lift-well enclosure of any Lift if such opening provides an access for exit from the building.
(13) In swing type doors the vision panel shall be so located that Lift operator can have convenient vision when opening the door from the Lift car side.
(14) A door open alarm shall be provided to draw attention when a car or landing door which has been left open in passenger Lifts.
(15) No landing opening for travel, shall exceed a maximum of 8 meters or two floors, whichever is less.
Locking devices for landing doors. – (1) Every landing gate or door shall be fitted with locking device which shall comply with the following requirements, unless otherwise permitted in writing by the Chief Inspector:
(i) Suitable means shall be provided so that it shall not be possible to open the gate or door from the landing side unless the Lift car is in the landing zone pertaining thereto. Provision shall be made so that landing gate or door may be opened in case of emergency or for inspection by the Inspector or by any authorized person, by means of a special key or other suitable device, irrespective of the position of the Lift car.
(ii) No Lift car shall be started or kept in motion, unless all landing gates or doors pertaining to the Lift are in the closed position.
[PART I
____
all not
the 13
the car
ug door
at any
sprung
x x 125
r doors
y fixed
tresses
s from
e from
d with
istance
s from
pivots,
(5) and
in the
closed
doors
tion of
pening
1 when
open in
which
r:
ng side
gate or
son, by
: in the
PART I]
17
(iii) The electrical and mechanical parts of all locking devices for gates or doors, shall be sufficiently strong so that reasonable wear may not cause an unsafe condition.
(iv) Every electro-mechanical lock shall be suitably encased and removal of any detachable cover fitted to such casing must not effect operation of the locking device. Where springs are used in locking devices, they shall be of compression type only and properly supported.
(v) The contacts of locking device for landing gates or doors shall be opened positively.
(vi) The locking device for landing doors shall be so designed that the lock contact is not closed until the door is closed, and the circuit shall not be completed until the leading edge of the door is within 5 millimeters of the nearest face of the door-jamb or when the leading edges of the center opening doors are within 5 millimeters contact of each other:
Provided that locking device shall not prevent the operation of the Lift whilst the emergency release push is in temporary use, or when the Lift car is being moved under the control of the leveling device.
(vii) Contact shall be of solid type pivoted, hinged on sliding and of sturdy construction.
· Provision shall be made on Lift operated from the car and landing to prevent the opening of any landing door when the car is passing that zone in response to a call from another landing;
(viii) The levers operating the mechanical part of the locking device shall be protected from interference from the landing side of the Lift enclosure.
(ix) Locking devices used with multiple panel doors shall lock all panels of the doors or only one panel provided that the interconnecting mechanism of door panels is so arranged that the locking of one will prevent the movement of all panels, notwithstanding the breakage of chain or rope used for interlocking the panels.
(x) When a door locking device is used on one panel of vertically bi-parting landing door reliance shall not be presses on gravity to keep the other panel closed.
Guide rails. - (1) Car and counter weight guide rails shall be of steel in all cases except where the nature of the processes carried on in the building render them unsuitable due to acid fumes for similar causes. In such cases prior approval of the Chief Inspector shall be obtained.
(2) Passenger and goods Lifts having rated speed of more than 0.50 meter per second, the car guide rail shall have their working surfaces machined.
(3) For passenger and goods Lifts having rated speed of more than 1.5 meter per second the counter weight guide rails shall have their surface machined.
(4) Round guide rails and cast iron guide rails shall not be used. 'T' section to be adopted shall be one of sizes specified in relevant Indian Standard or any other alternative section, provided they have adequate section modulus, moment of inertia and sectional area to withstand the forces resulting from the application of the car or counterweight safety devices.
(5) Guide rails shall be continuous throughout the entire length of the Lift well, and shall be so joined and fixed to their brackets which shall be of iron or steel so that the guide rails not deflect by more than 6 millimeters under round the clock operation. Wood blocks, plugs or similar methods shall not be used for fixing the guide brackets.
(6) Guide rails shall be of such length that it shall not be possible for any other car or counter weight shoes to run off the guide rails.
(7) Guide rails and their fixings shall be so arranged to withstand the action of safety gear when stopping a counter weight or a fully loaded car.
(8) Guide rails shall be held to their fastening by clips of such design that any rotary movement of the clip will not release the guide rails.
[PART I]
(9) The clips used for fastening the guide rails shall be of forged steel, formed steel or malleable iron or machined mild steel. The fasteners used shall conform to the relevant Indian Standard.
(10) If the guides are attached to overhanging stairs, the method of fixing shall be such that no vertical stress is transferred from the guides to the stairs.
(11) Guide brackets and shims if any, shall be of steel and shall not be directly supported and fastened to the Lift well enclosure wall unless such wall is of such construction and strength so as to adequately withstand the thrust imposed on the guides under all conditions of the Lift service. The fastenings shall be by means of bond blocks built in to the wall or expansion bolts or through bolts with metal plates of such thickness and size so as to adequately distribute the load on the wall.
Buffers. - (1)Buffers shall be provided below all Lift cars and counter weights in accordance with the requirements stated below:
(i) Spring buffers or their equivalent may be used with contract speed not exceeding 1.52 metre per second. Spring buffers shall be capable of stopping a Lift car with contract load from contract speed without permanent deformation.
(ii) Oil buffers their equivalent shall be used with Lift having a contract speed exceeding 1.52 metre per second. The maximum rate of retardation of oil buffers based on governor tripping speed shall be 24.54 metre per second and the minimum total stroke of such buffer shall be based on an average retardation of 9.81 metre per second based on governor tripping speed Means shall be provided for ascertaining the adequacy of oil supply in the buffers.
(2) Buffers shall be placed symmetrically with respect to the centre of the car platform or counterweight, as the case may be and these shall be so arranged that the car or counterweight under normal conditions of operation, does not strike them.
(3) Spring buffers shall be capable of supporting a static load equivalent to two times the weight of car and its rated load for car buffers and two times the weight of counter weight for counter weight buffers without being compressed solid.
(4) Spring buffers shall be compressed solid with a static load three times the weight of the car and its rated load for car buffers and three times the weight of counterweight for counterweight buffers;
(5) Oil buffers can be used for more than 1.5m / s speed with separate manual/auto reset electrical switch.
Counter-weights. - (1) All counterweights shall travel in rigid guides and in the Lift well or part of a Lift well to which these belong.
(2) If an independent Lift car counterweight is used, it shall not be of such weight as will cause undue slackening of any of the suspension ropes during acceleration or retardation.
(3) Counterweights consisting of multiple section with or without frames shall be secured by at least two tie rods passing through holes in all the sections, Such tie rods shall have lock nuts at each end and shall be further secured by suitable split pins. The factor of safety of the threaded portion of the tie rods shall be not less than 8.
(4) RCC casting filler weights which shall be suitably covered on all sides by M.S. sheet and counter weights consisting of multiple sections which shall be secured by steel plate and angle bolted with both the ends of counterweight frame. This arrangement shall be used for a contract speed of a Lift of maximum 1.0 m/s and capacity of maximum 6 passengers (408 Kg). Above the speed of 1.0 m/s, Cast Iron fillers are to be used.
Lift cars.- (1) Lift cars shall be provided with roof, enclosures and gates or doors. The enclosures of Lift cars intended to carry persons shall be not less than clear 2 metre in height. Perforated roof, where used, shall provide reasonable protection to person in the car against falling articles and the perforation shall be sufficiently close in mesh. The roof, solid or perforated, shall be capable of supporting the weight of a man weighing 68 kgs.
PART I]
achined
(2) Where the Lift car has a solid enclosure and doors, provision shall be made for adequate ventilation and every Lift car door shall be provided with suitable fire-resisting vision panel of adequate size(optional), when provided.
tress is
he Lift and the cans of ess andements
(3) No Glass shall be used in the roof of a Lift Car. No Glass shall normally be used as enclosure of a Lift Car. The provisions of this Sub-Rule may be released in the case of a Lift Car having said Glass Enclosure. Specification of such Glass shall be only Clear Laminated Safety Glasses transparent conforming to the existing bureau of standard specification.
(4) Each Lift car entrance shall be provided with a gate or door which shall cover the full height and width of the car opening. The top track of the gate or door shall not obstruct the car entrance.
(5) Lift car gates shall be of a close picket type and no openings shall exceed 6.4 cms in which between the vertical members of the gate when it is fully extended unless otherwise permitted by the Inspector of Lifts.
second nanent
(6) Each Lift car gate or door shall be provided with an electric switch which will prevent the Lift car from being started or kept in motion unless the car gates or doors are closed: Provided that slow speed leveling of the Lift car will be permitted from a position of 38 cms above or below the landing level with the gates or doors open.
second.
tre per metre of oil
(7) Lift car gate or door switches shall be opened positively.
(8) Every Lift car controlled by an Attendant shall be operated by a removable handle or key which shall remain at all times in the possession of the Attendant. The handle or key shall automatically return to the "Off" position when power is cut off. Landing gates such Lift cars shall also be opened only by a similar removable handle or key.
, as the ration, and its without
(9) Every Lift car shall be fitted with a suitable light for adequate illumination of the car and the light shall be kept burning during the whole time the Lift is available for use.
(10) Each passenger Lift car shall, where practicable light for provided with an emergency exit. Such exit shall be provided either in the roof or, where more than one Lift is installed in a Lift well, in the side adjacent to the adjoining Lift car. Where conditions do not allow the provision of an emergency exit, the car safety gear shall be of a type that can be released by raising the Lift car.
ed load
1.
(11) Top emergency exit panels shall not open inwards and shall be clear of all gear and equipments mounted on the top of the Lift car. The panels shall be held by suitable fasteners and so arranged that the panels can be opened from both inside and outside of the Lift car.
THE KOLKATAGAZETTE, EXTRAORDINARY, NOVEMBER 11, 2022
[PART I]
Load Plate.- (1) The contract load of the Lift in Kilograms or in other acceptable units shall be marked in a conspicuous position in every Lift car. For passenger Lifts, the maximum number of persons (other than the Lift Attendant) that the Lift car is permitted to carry safely shall also be similarly marked.
(2) The contract load of such Lifts shall not be less than 34 kgs or its equivalent for every 0.1 square metre of the Lift car floor area, measured inside the hand rails, if provided.
(3) No. passengers or load exceeding the number or amount marked shall be carried in the Lift car.
Explanation: For the purpose of calculation, the load of a person carried in the Lift car shall be reckoned as 68 kgs or its equivalent in the average.
Lift car frame.- (1) The car of every passenger or goods Lift shall be carried in a steel frame which shall sufficiently rigid and of adequate strength to withstand the operation the safety gear without permanent deformation.
(2) The deflection of the Lift car frame cross-head and the members carrying the Lift car platform shall not exceed 1/1000 of their span under static conditions with the contract load on the Lift car platform.
(3) Renewable guide shoes or guide shoes with renewable linings shall be provided at the top beneath the Lift car frame.
Safety gears.- (1) Every Lift suspended by ropes shall be provided with safety gear attached to the Lift car frame and should preferably to placed beneath the Lift car platform.
(2) A pawl or ratchet shall not be held to constitute a sufficient safety gear for Lifts.
(3) The safety gear shall be capable of stopping and sustaining the Lift car with full contract load in the Lift car.
(4) The safety gear shall operate to stop and sustain the Lift car in the event of failure of all suspension ropes, or in the event of the Lift car exceeding a predetermined speed in the descending direction when an over speed governor is fitted.
(5) No Lift car safety gear shall be permitted to stop an ascending Lift car. If an ascending Lift car is to be stopped on account of over speed, a safety gear shall be fitted to the counterweight for this purpose. An over speed governor may however be used to cause the motor control and the brake control circuits to be opened in the event of over speed in the ascending direction.
(6) The safety gear of every Lift having a travel exceeding 6 meters shall be operated by an over speed governor.
(7) The application of the safety gear shall not cause the Lift car platform to become out of level in excess of 4 cms. per metre measured in any direction.
(8) The motor control and the brake control circuits shall be opened at the time the safety-gear is applied.
(9) When the Lift car safety gear is applied, no decrease in the tension of any rope for applying the safety gear, or in the motion of the Lift car in the descending direction shall release the Lift car safety gear.
(10) No safety gear shall depend upon the completion or maintenance of an electric circuit for its operation.
(11) All safety gears shall be applied mechanically and shall operate independently of any springs used in its construction. Vibration of the Lift car frame shall not cause the safety gear to be applied.
(12) Any rope used for applying the safety gear shall be supported by its own pulleys and properly guarded. Such pulleys shall be mounted independently of any shaft carrying the Lifting ropes. Such guard shall be of steel or other suitable material.
(13) The gripping surfaces of Lift car or counterweight safety gears shall run free of the guides during the normal operation of the Lift.
(14) Any levers or cams operated by shafts shall be fasten to such shafts by means of keys in accordance with approved methods.
[PART I
____
ed in a
he Lift
of the
68 kgs
h shall
nation.
all not
Lift car
frame
lift car.
pes, or
speed
to be
control
vernor.
cess of
d.
y gear,
on.
I in its
L. Such
steel or
normal
e with
PART I]
21
(15) Safety gears shall be designed to grip each guide and to operate on both guides equally and simultaneously.
(16) All bearings for actuating drums and screw shafts in connection with the safety gears shall be of non-ferrous metal.
(17) The counterweight safety gear and governor has to be provided in case of hanging or floating pit.
(18) Combination of instantaneous and oil buffer safety gear for speed not exceeding 2.5 meter/second.
(19) Safety gears shall be of the following types :—
(i) Safety gears of the instantaneous type may be used on Lift car having a contract speed not exceeding 1 metre per second;
a. Safety gears of the instantaneous type may be used on Lift car having a contract speed not exceeding 1.27 metre per second;
b. Where the contract speed exceeds 1 metre per second safety gear of the following types shall be used;
(A) Gradual Wedge Clamp type.
(B) Flexible Guide Clamp type.
(20) The maximum stopping distances of Lift car with safety gears of gradual wedge clamp, and flexible guide clamp types with the contract load in the Lift car, and accordance with the table given below:
TABLE
[Speed in metre per second]
Maximum stopping distance with contract load
Minimum stopping distance with Attendant only in the Lift car
Gradual Wedge Clamp Type Metre
Flexible Guide Clamp Type Metre
Gradual Wedge Clamp Type Metre
Flexible Guide Clamp Type Metre
1.52
2.13
0.53
0.46
0.15
2.03
2.36
0.76
0.51
0.23
2.54
2.67
1.22
0.56
0.31
3.05
3.05
1.44
0.64
0.38
3.56
3.43
1.93
0.71
0.46
4.06
3.73
2.51
0 81
0.5311
Note.- The stopping distance shall mean the actual slide as measured by the marks on the guides.
NOTE: The following formula shall be used to determine the maximum and minimum stopping distance for gradual wedge clamp and flexible guide clamp type safeties for car and counterweight for all intermediate speeds:
S1 = 145V² +256
S2 = 51V² +12
S1 = Maximum stopping distance in millimeters
S2 = Minimum stopping distance in millimeters, and
(a) = Governor tripping speed meter per second
Governor.- (1) Governor shall be placed where it is not struck by the Lift car or counter weight in the event of over run.
(2) Governors for car safety gears shall be adjusted to actuate the safety gear at the following speeds:
(i) For rated speeds up to 1 Meter per second maximum governor tripping speed shall be either 140 percent of rated speed or 0.88 meter per second, whichever is higher.
22
[PART I]
(ii) For rated speed above 1 meter per second, maximum governor tripping speed shall be 115 percent of the rated speed plus 0.25 meter per second;
(iii) Minimum governor tripping speed shall be 115 percent of the rated speed.
(3) Each governor shall be marked with its tripping speed in meters per second.
(4) Where safety device other than the instantaneous type are provided, a switch, operated by the over speed action of the governor, shall be provided on it to open the motor control and brake control circuits at the following speeds before or at the time the governor trips:—
(i) In the down direction at not more than 90 percent of the speed at which the governor is set to trip in the down direction, and
(ii) In the up direction at not more than 100 percent of the speed at which the governor is set to trip in the down direction;
(5) Governor ropes shall be not less than 6 millimeters in diameter and shall be of iron, steel or phosphor bronze and of suitable construction. When replacement of original governor ropes becomes necessary, these shall be normally of the same size, material and capacity as the ropes originally supplied by the makers of the Lift. Before replacement by any other kind of rope, the suitability of such rope shall be tested to the satisfaction of the Chief Inspector.
(6) Governor ropes shall run clear of the governor jaws during normal operation of the Lift.
(7) The area of contact made by the governor rope and the governor sheave shall, in conjunction with the rope tension device, provide sufficient tractive effort to cause proper operation of the governor.
(8) Governor jaws and their mounting shall be so designed that any cutting, tearing or deformation of the rope resulting from their application shall not prevent proper operation of the safety gear.
(9) Governor gears should have self-lubricating bearings which do not require frequent attention.
(10) The motor control circuit and the brake control circuit shall be opened before or at the time the governor trips.
Machine room.- (1) All Lifts shall have machine rooms immediately over the Lift well, and this shall be arranged whenever possible without restricting the overhead distance required for normal safety precautions. Where the machine room is immediately over the Lift well there shall be permanent and direct access from the top of Lift landing. Alternative machine positions may be permitted by the Chief Electrical Inspector when there are special reasons justifying the same.
(2) All machine rooms shall be provided with adequate ventilation to dissipate the heat generated by the Lift equipment. For most single and double installations, a high and low louvered convection ventilation arrangement shall be provided. For groups of three or more Lift in one machine room, increased ventilation is necessary and forced ventilation shall be provided.
(3) All machine rooms shall be considered as plant space, and conditions provided to permit reliable operation of electrical switch gear and space around the machine shall in no case be less than 60 centimeters.
(4) Lighting shall be provided to give at least 200 lux around the controller and machine. The machine room walls, ceiling and floor shall be faced in dust-resisting materials, tiles, etc., or painted to stop dust circulation.
(5) The machine room shall be of strong construction. The floor of the machine room shall be capable of carrying the load of the Lift machinery and other equipment housed therein. Whenever a water tank is required to be constructed above or adjacent to the machine room, there shall be minimum separation 400 millimeters between the wall or slab of the machine room and the water tank.
(6) The Machine room shall be provided with reasonable access for the entry or removal of the equipments therein or of any part thereof. The height of the machine room shall be sufficient to allow any part of the equipment to be accessible and removal for repairs and replacement and in no case the height shall be less than 2.0 meters clear from the floor or the platform for machine elevator whichever is higher.
PART-I]
THE KOLKATAGAZETTE, EXTRAORDINARY, NOVEMBER 11, 2022
cent of
(7) The machine room shall be provided with fire proof and weather proof access doors opening outwards.(8) If the floor or platform of any machine room does not cover the entire Lift well, the open sides shall be provided with hand rails or shall be guarded by other suitable means.(9) The machine room shall not be used as a store room or for any purpose other than housing the Lift machineries and its associate apparatus and equipment. No inflammable or explosive material shall be kept in the machine room.(10) The machine room shall be kept locked which shall be accessible only to authorized persons. The key of the machine room shall be kept in the custody of the owner or his agent and shall be made readily available for repairs, maintenance or inspection.(11) The machine room shall be provided with an insulated portable hand lamp for examining the machinery.
speed
at the
in the
in the
bronze
(12) Thickness of machine room wall shall be of minimum 150 millimeters for R.C.C. structure or 250 millimeters for Brick construction.(13) The instructions in English or Hindi and Bengali for the rescue of persons traveling in the Lift by manual operation of brake in case of failure of Lift motor or power shall conspicuously be affixed in the machine room.(14) Machine room permanent staircase with hand rails of sufficient strength is to be provided.(15) Sufficient gap between machine room and water reserver has to be kept.
hall be
ie Lift.
tion of
e rope
39. Machine room less Lift.- (1) Lift Machine set shall be installed within the Lift Shaft on a suitable platform of adequate strength.(2) Easily accessible Emergency Door of adequate size having minimum height of not less than 1200 mm (with the provision of Electro Mechanical Locking Device) shall be provided in the Lift shaft for any access to the Lift Machinery for geared machine.
e rope
r trips.
40. Sheaves and pulleys.- Sheaves and pulleys shall be of cast iron and free from cracks, sand holes and other injurious defects. They shall have machined rope grooves. The traction sheave shall be grooved to produce proper traction and shall be sufficiently thick to provide for future wear in the groove. The deflector sheave shall be grooved so as to provide a smooth bed for the rope. Deflector or secondary sheave assemblies where used shall be mounted in proper alignment with the traction sheave.
ranged
re the
of Lift
THE KOLKATAGAZETTE, EXTRAORDINARY, NOVEMBER 11, 2022
[PART I]
(9) Means of releasing the brake in emergency shall be provided and the re-application of the brake ensured. It shall be ensured that hand winding of Lift, by releasing the brake is done only by trained person.
(10) No brake shall be released in normal operation until power has been applied to the motor.
(11) Any emergency release device fitted to a brake shall not be capable of holding the brake in the off position during normal operation.
(12) The sheave, drum worm wheel or spur gear of any Lift machine shall be fixed to its shaft or driving unit either by means of sunk keys or splines according to Indian standards or shall be secured to a flange forming an integral part of the shaft or driving unit by means of turned tight fitting bolts. No set screw fastenings shall be used in lieu of keys or other positive connections.
(13) All machines, pulleys, over speed governors and similar units shall be so supported and held as to prevent any of these machineries or parts thereof from becoming loose or displaced affecting their safe working. Supporting beams shall be of steel or reinforced concrete.
Suspension.- (1) Chains shall not be used for the suspension of a Lift. Not less than three independent suspension ropes shall be used for car or counterweight of any Lift with traction drive.
(2) In the case of traction drive, the factor of safety shall be based on static contract load plus the weight of the Lift car and accessories. In case of drum type drives, the factor of safety shall be calculated with dynamic conditions.
Explanation: For the purposes of these Rules, the factor of safety shall be as under:
well to
kening
(12) Emergency exit panels shall not be opened or removed while the Lift car is in motion and suitable means shall be provided to prevent the Lift from being operated when the emergency panel is opened or removed.
ie rods further ss than
(13) Every Lift car on an automatically controlled Lift shall be provided with an emergency alarm signal which can be operated by a push button in the Lift car and shall be clearly audible outside the Lift well in order that assistance may be obtained in case of a breakdown or failure between the floors. Every such push button shall be clearly marked.
/eghts ends of 1/s and used.
(14) Where Lift car leveling device are used, the Lift car platform shall be fitted with a substantial apron so as to prevent any object from being trapped between the Lift car platform and Lift landing while the car is within that landing zone.
ft cars provide lose in
(15) Lift car platform shall be so designed and of such construction as to meet any particular condition of loading. The Lift car floor of passenger Lift shall be of smooth non- slip surface.
(16) Lift landing door seals should be leveled with the floor level.
(17) Toe guard should be minimum of 400mm.
(18) Fascial plate should be provided.
special
e Lift
41. Lift machine.- (1) No friction gearing, chain, clutch or chain driven mechanism shall be used for connecting the main driving gear to the traction sheaves;(2) The motor of each Lift machine or the worm shaft shall be arranged so as to provide hand winding/brake release facilities and shall be suitably marked for the direction of up and down travel of the Lift. All the motors should be of S-4 grade or above duty cycle.(3) Electric Lift machine shall be provided having brakes released electrically. Independent circuit for brake operation is to be provided.(4) Traction machines for Lift shall be equipped with the brakes applied automatically by means of springs in compression only or by gravity when the operating device is in the "off" position or in the event of the power being cut off due to any cause.(5) No single earth fault, short circuit or counter electromotive force shall prevent the brake from being applied during normal operation.(6) The brake shall be designed to have a capacity sufficient to hold the car at rest with 125 percent of its rated load.(7) No toggle or other device which is dependent upon impact operation shall be used to hold of the brake.(8) Brake of passenger and goods Lift shall have at least two brake shoes and the lining used shall be incombustible material.