- Lift wells. -(1) Every Lift well intended for the installation of the Lift or any equipment necessary for its maintenance shall be exclusively reserved for that purpose and shall not be used for any other purpose;
(2) The inner sides of a Lift well shall, so far as practicable, form a smooth, continuous flush surface devoid of projections or recesses. Where any projections extending inwards from the general surface of the enclosure at or near openings or landing cannot be rendered flush, then they shall be leveled on the underside to an angle of not less than 60 degree from the horizontal by means of metal plates, cement rendering, or other suitable fire resisting materials.
(3) Where there is more than one Lift in common well, a width of minimum allowance of 100 millimeters for separator beam shall be made.
(4) Where there is more than one Lift in common well, a suitable separator screen throughout the whole height of Lift well having adequate strength shall be fixed in the Lift well to protect the person working in the Lift well or in the Lift car, from accidental contact with counter weights and other Lift car at any state of their travel.
(5) No room, passage or thorough fare shall be provided under any Lift well except in case of the Lift having counter weight fitted with over speed governor safety device.
(6) Where a Lift car leveling device is operative with the Lift car gate opening such interior surfaces shall always form a smooth flush surface below each landing level for a depth to at least the depth of the car leveling zone plus distance through which the Lift car may travel of its own momentum when power is cut off.
(7) Sufficient space shall be provided between the guides for the car and the side walls of the Lift well enclosure to allow safe and easy access to the parts of the safety gear for their maintenance and repairs.
[PART I]
(8) Every Lift well, together with the whole of the equipment and apparatus contained therein, shall be rendered fire resisting to the greatest possible extent.
(9) A notice with the word "Lift" shall be placed on the outside of each landing door.
(10) (10) The Lift well shall conform to specifications laid down by Bureau of Indian Standards specification BIS-14665 (Part-1)-2000.
- Lift wells enclosures. – (1) Except as provided in sub-rule (2) every Lift well shall be protected by a substantial fire resisting enclosure extending on all sides and fitted with gates or doors. The enclosure shall be so constructed that no person may fall down in the Lift well or come into contact with any moving part of the Lift when the gates of doors are shut.
(2) Where fire-resistance construction cannot be provided, the Lift well shall be enclosed to a height of not less than 1.83 meters or such greater height as may be recommended by the Chief Electrical Inspector.
(3) Where wire grill or similar construction is used, the mesh or opening shall not be greater than 3 centimeters and the Lift well enclosure shall be of sufficient strength to resist accidental impacts by users of the staircase or adjoining floors, and in the case of goods Lift, by movements of materials in the vicinity.
(4) Where the clearance between the inside of an open type Lift well enclosure and any moving or movable part of the Lift equipment or apparatus is less than 5 centimeters, the openings in the enclosure shall be further protected by netting of square mesh not greater than 13 millimeters and of wire not smaller than 1 millimeter or in a manner approved in writing by the Inspector of Lifts.
(5) The Lift well enclosure on the sides used for loading and unloading shall not be at a distance of more than 13 cms from edge of the Lift car platform.
(6) There shall be no opening in the Lift well enclosure permitting access to the Lift car by passing under the counterweight.
(7) In the construction of Lift well enclosure glass shall not be used. However condition may be relaxed in case of specially designed, well protected, fully transparent laminated type safety glass construction as may be permitted by the Chief Electrical Inspector. A certificate from the qualified structural engineer regarding the proper fixation in respect of such type of construction shall be submitted.
(8) Lift wells and wells for the counterweight, if located independently of the Lift well shall be adequately protected by means of suitable enclosure work which shall be extended on all sides from floor to ceiling.
(9) In all counter-weight wells located independently of the main Lift well, suitable access shall be provided for the inspection, maintenance and repairs to counter-weights, wire ropes and their anchorages, guides and guide supports.
(10) All such doors giving access to such counter-weight wells shall be provided with electromechanical locking devices.
(11) No counter weight shall be allowed to travel in any Lift well or part of any Lift well other than that to which it belongs.
(12) The Lift well enclosure on the sides facing any Lift car entrance shall so far as is practicable, be not more than 25 millimeters from the edge of the Lift car platform.
(13) The walls enclosing Lift well in the buildings having height more than 30 meters shall have fire resistance of not less than two hours. The Lift well shall have permanent vents immediately under the machine room not less than 0.2 square meter in clear area.
(14) The Lift well for fire Lift (a Lift to enable fire brigade personnel to get to the upper floors with the minimum delay and to be used exclusively by firemen in an emergency and directly accessible to every landing on every floor), in the building having more than 24 meters height shall be segregated from the other Lift wells by means of brick masonry or R.C.C. wall of a fire resistance of not less than two hours.
(15) Fire Lift in a building having more than 24 meters travel, shall work at such speed so as to reach the top floor from ground level within one minute.
27..
[PART I] —— ndered . ication stantial tructed e gates not less meters aircase ple part further limeter han 13 der the in case nay be ing the quately ling. led for es and ocking which t more nce of om not minimum a every ells by p floor
PART I]
15
(16) Thickness of the Lift enclosure wall shall be of minimum 150 millimeters for R.C.C structure or 250 millimeters for brick construction.
(17) Capsule Lifts as well as glass Lifts shall not be allowed to be installed "open to sky". Whenever installed in house, following provisions shall apply.
(i) Lift well enclosure of this type of Lifts shall have partial covering on one side in which capsule Lift protruding structure moves. The area immediately beneath this side of the Lift enclosure shall be declared as no man area and shall be provided with adequate guarding.
(ii) In case of glass Lift, one side of the Lift enclosure shall have clear laminated safety glasses of minimum 8 millimeters thickness. The area beneath this side of the Lift enclosure shall be declared as no man area and shall be provided with adequate guarding.
- Lift pit. - (1) A pit of adequate depth shall be provided for every Lift below the level of its lowest landing.
(2) The Lift pit shall be so constructed as to be capable of withstanding the impact of the Lift car with the rated load or the impact of the counter-weight when either is descending at rated speed or at governor tripping speed in case governor operated safety gear is used.
(3) The Lift pit shall be of adequate size, treated with water proofing compound, net cemented and shall be maintained in a dry and clean condition. The floor of the Lift pit shall be approximately level and where necessary provision shall be made for permanent drainage.
.(4) Where the pit depth exceed 2 meter, suitable access shall be provided by a ladder or any other suitable device and light point with a switch along with a car control switch at entrance level shall also be provided for facility of maintenance and repair work.