21 Requirements of sites : —
Any piece of land can be used as a site for construction provided –
(i) the proposed use conforms to the Aizawl Master Plan and Zonal Development Plan prepared under the Act;
(ii) the site is properly drained or capable of being drained;
(iii) the site is accessible by any means of passage, whether private or public, for vehicles or for pedestrians and includes any street, and
(iv) the site is not an active hazard-prone area such as landslide, subsidences, mass movement, etc.
22 Set Backs and Open Spaces:
(i)The following setbacks and open spaces are mentioned below
| Items | As per Regulations | |
|---|---|---|
| <sup>k</sup>c | a) b) c) d) e) | Small Plot area above (46.45 sq.m to 93 sq.m) : 1.2m Plot area above (93 sq.m to 130 sq.m) : 1.5m Plot area above 130.00 sq.m : 2.0 Plot depth less than 9m : 1.2.m Plot having road reserve of 3-5m or more : |
| a | (provided formation width of road fronted is at least 6m) : 0.9m | |
| B | ||
| t | f) | Plot having road reserve of 5m or more : |
| S<sup>e</sup> | (provided formation width of road fronted is at least 6m) 0.6m | |
| t | g) | Plot situated along on existing row of commercial buildings : |
| <sup>n</sup>o F<sup>r</sup> | h) | to be decided on merit of individual case. irregular shaped plots: The average of the prescribed values |
| i) | subject to a minimum of 0.6m Plot where immediate neighbouring plots on the both adjacent sides have constructed their buiding up to the edge of the road fronting their plots and up to their plot lines at the sides: 1.2m front setback (from the road reserve, if any). | |
| a) b) c) | Small plot area above (46.45 sq.m to 93 sq.m) : 0.6m Plot area above (93 sq.m upto 130 sq.m) :0.9m Plots area above 130.00 sq.m : 1.2m | |
| k c | d) | Plot width upto 9 m : 0.6m |
| a | ||
| B | e) | Plot is situated along an existing row of commercial buildings: |
| t | No setback required. | |
| S<sup>e</sup> | f) | Irregular shaped plots: The average of prescribed values |
| e | subject to a minimum of 0.6m. | |
| <sup>d</sup>i S | g) | Plot where immediate neighbouring plots on both adjacent sides |
| have constructed their building up to the edge of the road fronting their plots and up to their plot lines at the sides: 0.6m (side and rear set back). | ||
| <sup>k</sup>c | a) | Small plot area above (46.45 sq.m to 93sq.m) : 0.6m |
| r a | ||
| <sup>a</sup>e <sup>B</sup> | b) | Plot area above (93 sq.m upto 130 sq.m) : 0.9m |
| R <sup>t</sup><sub>e</sub> | c) | Plots area above 130.00 sq.m : 1.2m |
| S | d) | Plot width upto 9 m : 0.6m |
(ii) In case where the site fronts two or more streets, the frontage would be on the street having the longer or longest width. In cases where the streets are of the same width, then the longer/ longest side of the plot will decide the frontage and open spaces.
(iii) The minimum distance between any two or more buildings within one plot shall be 2.4 m if one of the buildings or both the buildings is/are multi-storied; otherwise, it shall be 1.2m provided that in the former case where the buildings are not parallel, the average of the prescribe distance may be acceptable with a minimum distance of 1.2m.
(iv) For plots above 130 sq. m not fronted by a vehicular access/ approach, the front setback shall be relaxed to 1.2m. For plots above 93sq.m and upto130sq.m, the front setback may be 0.90m. For small plots, the front setback may be relaxed to 0.6m and It may however be noted that for the various plot sizes the corresponding side and rear setbacks shall remain the same.
(v) In respect of a plot situated along an existing row of commercial buildings, setbacks may be decided on merit of individual case after taking the recommendation of the Committee on Relaxation into consideration.
(vi) For vertical extension/addition of an existing building wherein any further lateral development is restricted by the Regulations, the existing structural columns and non-cantilevered beams lying in the specified side and rear set backs may be allowed to continue in the vertical extension/addition. No other structure except structural columns and non-cantilevered beams, floor slabs and safety measures such as railings shall be allowed within the prescribed set back area or side set back area.
(vii) Steps or ramps constructed along the existing ground profile or slope may be allowed in the prescribed set back areas. In addition, building services such as underground water tanks, septic tank, soak pit, inspection chamber, etc may be allowed within the prescribed set back areas, provided that such structures remain flushed with the adjoining ground/slope.
(viii) Chajjas, sunshades and rain gutters may be allowed to project up to 0.45m (1½ ft.) within the prescribed setback area, provided that there is a minimum of 1.2 m wide setback on the respective side.
(xi) In case of very small plots (less than 46.45 sq m) setbacks may be decided in consultation with leaders of the Local Council.
(x) If, in the interest of the public, it becomes necessary to prescribe a larger set back (that is to say, the front, sides and rear open spaces),taking into consideration the Master Plan/Zonal Development Plan, the size of the plot, the area in which the building is situated, the height of the building or any other relevant factor, the Aizawl Municipal Council shall have the power to do so and the reason or reasons thereof shall be communicated to the applicant in writing.
23 Minimum plot sizes:
(i) For residential: - The minimum plot size shall be 93 sq.m, with a minimum width of 8m.
(ii) For commercial:- The minimum plot size shall be 50 sq.m, with a minimum width of 6m.
(iii) For service, small-scale and cottage industries:- The minimum size of plot shall not be less than 50 sq.m. For automobile workshop, the minimum plot size shall be 300 sq.m.
(iv) For medium industry:- The minimum size of plot shall be 1800 sq.m.
(v) For auditorium, museum, library: The minimum size of plot shall be 800 sq.m.
(vi) For LIG / EWS Housing:- The minimum plot size shall be 46.45 sq.m per unit.
Explanation:
For the purpose of this regulation, ‘service industry’ means an industry which is mainly small scale and is concerned with repair, maintenance, servicing, etc. and not employing more than 25 persons and not using power of more than 10 horse power (HP) (7.5 KW).
24.Distance from Electricity Lines:
No roof of a building shall be made, and no verandah, balcony or the like shall be allowed to be erected or re-erected or new addition or alteration made to a building within the distance quoted below in accordance with the Indian Electricity Rules, 1956 :
| Sl.No | Distance from Electricity Lines | Vertically | Horizontally |
|---|---|---|---|
| 1 | Low and Medi um Vol tage l i nes and services l i nes. | 2.5 metres | 1.2 metres |
| 2 | High vol tage l i nes up to and i ncl udi ng 33.000V. | 3.7 metres | 2.0 metres |
| 3 | Extra high vol tage l i nes beyond 33.00V. | 3.7 metres (plus 0.3m for every additional 30,000v or part thereof) | 2.0 metres (plus 0.3m for every additional 30,000v or part thereof) |
- Minimum Off-Street Parking Space:- The off-street parking space shall be as shown below:
| Sl.No | Type of occupancy | One parking space for every | Size |
| 1 | Residential A | 110000 s spq..mm of floor area | 2.5m x 4.5m |
| 2 | Residential B | -do- | -do- |
| 3 | Special Residential | 200 sq.m of floor area | 2.5m x 5m |
| 4 | Educational | 75 sq.m of floor area | -do- |
26 Requirements of Parts of Building:
(1) Size and Area requirements: The sizes and areas of some parts of a building may be as follows:
| Sl.No | Parts of building | Minimum width | Minimum Floor area | Minumum Floor height | ||
| 1 | Habitable room | 2.4m | 7.5 sq.m | 2.4m | ||
| 2 | Kitchen | 1.8m | 5.0m 5.0 sq.m | 2.4m | ||
| 3 | (a) | Bathroom (single) | 1.2m | 1.8m1.8sq.m | 2.2m | |
| (b) | Combined bath & Water Closet | 1.2m | 2.8sq.m | 2.2m | ||
| ( c) | Water Closet | 0.9m | 1.1 sq.m | 2.2m | ||
| 4 | Mezzanine floor | Maximum coverage of 33.3% of Plinth area of the building | 9.5 sq.m | 2.2m | ||
| 5 | Loft | Maximum coverage of 26% of room size | - | 1.5m | ||
| 6 | Ledge | Maximum coverage of 25% of room size | - | 2.2m | ||
| 7 | Parking Space | - | a) | Residential 2.5m x 4.5m | 2.4m | |
| b) | Others 2.5m x 5.0m | 2.4m | ||||
| 8 | Parapet | - | - | 1.0m | ||
| 9 | Staircase | Maximum height of of Riser: 20cm (8") | Width of tread: 25.4cm (10") | 1.2m. 2.2m below landing of a staircase. | ||
Provided that other than those mention above, the requirement of parts of buildings may be regulated as per the provisions of the National Building Code, 2005.
(2) Other requirements of Parts of Building:
(a) Plinth: The plinth of any part of a building may be raised above ground level or road level so that adequate drainage of site is assured. This may preferably be not less than 0.45 metre. Every interior court-yard or garage may be raised by a minimum of 0.15 metre above ground level and may be satisfactorily drained.
(b) Roofs: The roofs shall be so constructed to permit effective drainage of the rain water thereof by means of rain gutters and closed conduits of suitable material and adequate capacity, joined and fixed so as to ensure that rain water is properly discharged at ground level by pipe and dampness does not occur in any part of the walls or foundations of the buildings or those of adjacent buildings, and no spout should be allowed to drain into the road or public area or within the adjacent compound or building. For buildings with RCC roofing, water proofing material shall be used at the roof level.
27 Provision of Lift:
Provision of lifts shall be made mandatory for special residential, mercantile, institutional and government or semi-public buildings having four floors or more. In counting the number of floors for provision of lift, a floor which has a separate and independent entrance shall not be counted.
28 Exits and Means of Access:
An exit may be a doorway, corridor, passage-way to an internal staircase or external or to a verandah or roof or terrace having access to a street. Lift and escalator shall not be considered as exits.
(i) Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of the occupants in case of fire or other emergencies.
(ii) Exits shall be arranged so as to provide continuous means of access to the exterior of a building or an exterior open space leading to a street, without passing through any occupied unit.
(iii) Exits shall be so located that the travel distance on the floor shall not exceed 22 metres in the case of residential and public buildings and 30 metres in the case of commercial, industrial and other types of occupancy.
(iv) The width of any exit shall be not less than 90 cm.
29 Other Requirements of Exits:
(1) Doorways: The minimum width of an exit doorway shall not be less than 90 cm. and the minimum height shall not be less than 195 cm.
(2) Stairways:
(i) The minimum width of an internal staircase shall be 120 cm., except in the case of residential dwellings where the minimum width shall be 100 cm.
(ii) In the case of residential buildings, the minimum width of treads without nosing shall be 25.4 cm for an internal staircase. In case of other buildings, the tread shall be 30 cm.
(iii) The maximum height of riser shall be 20 cm.
(iv) Handrail shall be provided with a minimum height of 90 cm. from the centre of the tread.
(3) Fire escape or external stairs: All buildings with Ground + three floors shall have at least one fire escape other than the main stairs. In large buildings, the fire escape placements shall be dictated by the traveling distance, the maximum of which should not be more than 22 metres.
Provided that if a floor of a house has a separate and independent entrance, no separate fire escape shall be necessary for that floor.
Fire escapes shall be regulated as under:
(i) All fire escapes shall be directly connected to the ground.
(ii) Entrance to fire escapes shall be separated and remote from internal staircase.
(iii) The route to fire escapes shall be free of obstructions at all times, except a doorway leading to the fire escape which shall have the required fire resistance.
(iv) Fire escapes shall be constructed of non-combustible materials.
(v) It shall have straight flight not less than 75 cm wide with 20 cm tread and riser not more than 19 cm. The number of risers shall be limited to 16 per flight.
(vi) The height of hand rails shall not be less than 100 cm.
(4) Spiral Stairs (Fire Escape): The use of spiral staircase shall be limited to low occupant load and to buildings of the height of 9 metres unless it is connected to platform such as balconies and terraces.
(5) Ramps: Ramps shall be provided within or as an appendage to a building if required by the function of the building. In general, ramps shall have a minimum width of 1.5 metre and a maximum slope of 1 vertical: 10 horizontal. In special cases, steeper slopes may be allowed but in no case greater than 1: 6. In case of hospitals, the minimum width shall be 2.2 metre. The ramps shall be finished with non-slip surface and handrails with a minimum height of 90 cm. shall be provided on the free edges. Level platforms of at least 1.8 metre x 1.8 metre size shall be provided at every turn and at intervals of at least 9.5 metre for the purpose of rest and safety. Each ramp shall have at least 1.8 metre x 1.8 metre size platform at the top and bottom.