(A) Regarding submission of plan by Govt. Department, the procedure shall be as follows:
(a) All building whether by Government or Private Architects shall in all its aspects confirm to the byelaws.
(b) The Central/State Govt. or A&N Administration shall designate an authority within its own department to issue a certificate specifying that the bye-laws have been followed in all its aspects. The plan then that the
Procedure for Construction By govt.Agencies
Fees
3.8
bye-laws have been followed in all its aspects. The plans then need not be submitted to the local authority for approval.
(c) The certificate mentioned in 3.7 (A) (b) above shall preferably be given by a person not directly connected with the preparation of plan and specification.
(d) All Plans and other details shall be submitted to the local authority for information and record.
(e) In the case of construction of defence departments, layout plan should be submitted and general indication given whether they are residential or not so that the local authority can estimate the requirements of water, electricity and sewerage disposal.
No notice as referred to in 3.1 shall be deemed valid unless and until the person giving notice has paid the fees prescribed by the authority and an attested copy or duplicate copy of the receipt of such payment is attached with the notice.
3.9 (i) The fees as mentioned in 3.1 shall be charged in terms of the floor area of the building. In the event of a “building permit” is not issued the fees so paid shall not be returned to the occupier by he shall be allowed to resubmit it with 10% of fee described under rule 3.8 after complying with all the objections raised by the authority within a period of 6 months from the date of rejection after which fresh fees shall have to be paid.
(ii) The building permit fees for all buildings shall be as under:
(a) All kind of residential building
Total covered - upto 150.00 sq.mtrs - Rs.04.00/M2
Area on all - upto 300.00 sq.mtrs - Rs.10.00/M2
Floors - above 300.00 sq.mtrs- Rs.20.00/M2.
(b) All Kinds of commercial building
Total covered - upto 150.00 sq.mtrs - Rs.40.00/M2
Area on all - upto 300.00 sq.mtrs - Rs.60.00/M2
Floors - above 300.00 sq.mtrs - Rs.120.00/M2.
Part IIProcedure for Obtaining Building Permit for the Erection of Buildings and Execution of Works.
Notice: 3.1 Every person, who intends to construct, reconstruct, alter or add to a building or demolish any building shall give notice to the authority for the approval of the site and for permission to execute the work in the forms specified in appendix ‘A’ with such variation as circumstances may require.
Site Plan: 3.2 It shall be accompanied by:
(i) Land Records- Revenue map and records entry pertaining to the plot on which building is to be constructed/ reconstructed altered or added, issued by the competent authority.
(ii) A Plan or Plans (in triplicate) of the building to be constructed, Reconstructed altered or added to draw or reproduced in a clear and legible manner of suitable or durable material and showing a ground floor plan, elevation or each floor and sections of the building and complying with the requirements specified in appendix ‘C’ and
(iii) A specification (in triplicate) complying with the requirements Specified in the Appendix ‘D’ as far as may be necessary.
(iv) An undertaking that coral shall not be used as a building material in any form.
3.3. All the plans shall be duly signed by the occupier/authorized agent and the registered architect, Regd. Or Licensed Supervisor and should indicate their names, address, qualifications and license number.
3.4 Every person who has given notice to the authority for the approval of the site and for permission for execution of work shall inform the authority in writing the date of commencement of the work and on completion of plinth level, roof level and report of completion to facilitate the authority for inspection.
Colouring the Plan 3.3 (A) The colours to be used in the plans shall be as in the following table.
Qualification of Regd.
Architect Regd.
Engineer Licenced Supervisor
Item
Site Plan
Building Plan
Amonia print white plan
Blue print
Amonia print white plan
Blue print
1.
Existing works
Black (out line)
White
Black
White
2.
Proposed works
Red (filled in)
Red
Red
Red
3.
Drainage & Sewerage work
Red dotted
Red dotted
Red dotted
Red dotted
4.
Water supply work
Black dotted thin
Black dotted thin
Black dotted thin
Black dotted thin
5.
Works proposed to be dismantled
Yellow hatched
Yellow hatched
Yellow hatched
Yellow hatched
6.
Open spaces
No colour
No colour
No colour
No colour
7.
Plot lines
Thick black
Thick black
Thick black
Thick black
8.
Permissible building line
Thick dotted black
Thick dotted black
--
--
9.
Existing street
Green
Green
--
--
10.
Future street if any
Green dotted
Green dotted
--
--
11.
Work to be regularized or diviation made
Red dotted
Red dotted
Red dotted
Red dotted
Drawing etc. 3.4 Every building work for which permission is sought under the Bye-Prepared by laws shall be designed and supervised by the Regd. Licenced Architect/Regd. Engineer/Licenced Supervisor. Qualification Architect etc. which a person shall have for registration as Reg-streed Architect/Regd. Engineer/Licenced Supervisor within the jurisdiction of the Port Blair Municipal Board shall be mentioned in 3.5(i) to 3.5(iii)
3.5 (i) The minimum qualification of a Regd. Architect Shall be a Regd. Architect with the COUNCIL of Architecture under the Architects Act, 1972 (20 of 1972).
(ii) The minimum qualification for a registered Engineer shall be the corporate membership (civil) of the institution of Engineer (India) of such degree or Diploma in civil, Municipal or Structural Engineering which makes him eligible for such membership.
(iii)The minimum qualification for Licenced Supervisor shall be: -
(a). 3 years Architectural Assistantship of Intermediate in Architecture or
(b). Diploma in Civil Engineer; or
(c). Certificate course in Draftsmanship in Civil Engineer form I.T.I. or equivalent with 5 (five) years experience.
3.5 (A) The Authority may decline to accept any plan, section or specification which does not bear the signature of a Reg. Architect, Regd. Engineer of Licensed Supervisor in token of its having been prepared by the Licensee or under his supervision.
Competence: 3.5 (b) (1) ARCHITECT/ ENGINEER
The licenced Architect is competent to carryout work related to building permit as give below and will be entitled to submit:
(a) All plans and related information connected with building permit.
(b) Structural detail and calculation for building on all plots.
(c) Certificate of supervision for all building.
(d) All Layout plans.
(ii)supervisor.
The Licenced Supervisor will be entitled to submit all plans and related Information connected with Building permit on plots up to 200 sq. Mtrs. And up to two storeys only. LICENCING 3.5 (c)
The qualified technical personnel or group as given in 3.5 shall be licensed with the authority as prescribed in appendix-k and the license shall be valid for one calendar year ending 31st December after which it shall be renewed annually.
4Health Sanitation and Other Requirments
4.1 Any land passage or any other area within the cartilage of a building shall if the Authority so requires be effectively drained by surface water drains or other means.
4.2 No verandah, Balcony or the like shall be allowed to be erected or re-erected or any additions or alteration made to building within a distance coated be below in accordance with the current Indian Electricity rules and its amendments from time to time between the building and any over head Electric supply lines.
VerticalClearanceFrom the highest point
HorizontalCleaaance fromthe nearest point
a)
Low & medium Voltage lines and Service lines
2.5
1.2
b)
High voltage line Up to and including33,000 volts
3.7
2.0
c)
Extra high voltage Lines beyond 33,000 Volts
3.7(+0.3for every additional33 KV)
2.0 (+0.3 for every additional 33KV)
(Plus 0.3m for every additional 33,000 volts or part thereof)
4.3 No building shall be constructed on any site, any part of which there is deposited refuse or other offensive matter objectionable to the Authority until such refuse has been prepared or left in manner suitable for building purposes to the satisfaction of the Authority.
4.4 No site which is situated with in a distance of 90 m from a place used as a burial or burning ground shall be used for the construction of any building without the previous approval of the Health Officer & no building intended for human habitation with in burning place or ground was closed or burning or burial place or ground shall be reconstructed or added to without the previous approval of the Health Officer.
4.5 No site shall be approve for construction of building unless provision of Suitable measures for checking the erosion of soil and sliding due to excavation are made to the satisfaction of Authority.
4.6 Every person who constructs, reconstructs, Alters or adds to a building shall carry out such measures as far as possible to conserve and protect all existing trees with a diameter of 30 cm
Preservation of Contamination to Fresh water source
4.7
Foundation
4.8
5.1
5.2
5.4
Requirements Of plinth
6.1
6.2
and more within his site provided That all dangerous trees which are likely to cause damage to his own all adjoining properties shall be caused to removed. The Municipal Board shall consult the town-planning branch of A.P.W.D/Directorate of town planning in giving permission for removal.
Every person who constructs, re-constructs, alters or adds to a building shall wherever the site is within 15m of any tank, reservoir, water course, river fresh water channel or well, carry out such measures as may be necessary or as the authority may direct for the purpose of preventing any contamination of any risk of the drainage of building passing into such tank reservoir, water-course, river, fresh water channel or well
Rain Water Harvesting
Every person who constructs, reconstructs, adds to a building or alters it, shall provide a proper spout /tank for collection of rain water which shall be utilized for various domestic purpose other than drinking.
(c) Public Buildings
Total covered
Area on all - upto 150.00 sq.mtrs - Rs.10.00/M2
Floors - upto 150.00 sq.mtrs - Rs.50.00/M2
(d) Additions, - 50% of original permit Alterations & Fee. Revisi
Revisions
(e) Revalidation - 25% of the original permit fee per year after expiry of the original building permit.
Prevention of permit
- 10% in case the revalidation sort for before the expiry of the original building permit.
NOTE: In no case the building permit fee as specified above shall be less than Rs.100/-
3.10. notifications of stages :
(1) As work progresses under a building permit, the holder thereof shall cause the Authority to be notified at the following stages of constructions:
(a) Upon commencement of the work.
(b) Upon completion of the footings and before erection of the foundation walls; and
(c) Upon total completion of the work authorized by the building permit and before occupancy in the form prescribed in Appendix-‘E’.
(2) inspection at the stages referred to as (a) and (b) of sub-rules (1) shall be made by the Authority or any other Officer authorized by him within 7 days following the receipt of the Notice after which period the owner will be free to continue the construction according to the sanctioned plan. At the first inspection the Authority or the Authorised Officer shall determine to the best of his ability that the building has been located in accordance with the site plans and yard area complying with the requirement of these rules. The final inspection at the stage indicated in clause (c) of sub rule (1) shall be made within 21 days following the receipt of Notice for the grant of occupancy Certificate.
3.11. The sanction once accorded shall remain valid for 2 Years.
3.12. If during the construction of a building any departure of a substantial nature from the sanctioned plan in intended to be made, sanction of the authority shall be obtained before the change is made. The revised plan showing the deviation shall be submitted and procedure laid down for the original plan apply to such amended plan.
3.13 The authority may revoke any permit issued under the provisions of the Bye-Laws Wherever there has been any fake statement or misrepresentation of any material fact in the Application on which the permit was based.
3.14 The Authority may either sanction or refuse the plans and specifications or may sanctioned them with such modification and direction as it may deem necessary and there upon shall communicate its decision to the person giving the notice, in Appendix-‘E’ or ‘J’ as the case may be.
3.15 If within 60 days of the receipt of the notice under 3.1 of the bye-laws, the authority fails to intimate in writing to the person, who has given the notice of its refusal or sanction, the notice with its plans , statements shall be deemed to have been sanctioned, provided that the fact is immediately brought to notice of the Authority in writing by the person who has given notice and having not received any information from the authority within 30 days of giving such written notice subject to the conditions mentioned in this clause nothing shall be constructed to authorized any
Ground for refusal of Building plan of work
3.17
Temporary Occupancy
person to do anything in contravention of or against the terms or lease of titles of the land or any other regulations, bye-laws ordinance in operation, on the site of the works.
3.16 In the case of refusal, the authority shall quote the reason and relevant section of the bye-laws which the plan contravenes. The authority shall be as far as possible point out the objections to the plan and specifications in the first instance itself and ensure that no new objection are raised when they are resubmitted after compliance of earlier objections.
(A) The grounds on which the sanction of a building plan or work may be refused shall be the following namely:
(a)That the building or work or the use of the site for the building work or any of the particulars comprised in the site plan, ground plan elevation section or specification would contravene the provisions of any bye-laws made in this behalf or any other law or rule, bye-law of order made under such other law.
(b)That the notice of sanction does not contain the particulars or is not prepared in the manner required under the bye-laws made in this behalf.
(c)That any information or documents required by the Secretary/ an officer authorized by the Municipality under the Regulation or any bye-laws made there under has or have not been duly furnish ed.
(d) That in case falling under the section/layout plans have not been sanctioned in accordance with the bye-laws.
(e) That the building or work would be an encroachment on Govt. Land or land vested in the Municipality.
(f) That the site of the building or work does not abut on a street or projected on street and that there is no access to such building or work from any such street by a passage or pathway appertaining to such site.
The Secretary or any officer authorized by him with the approval of the Chairperson shall communicate the refusal along with the reason there of to the person who has given the notice.
3.18 Once the plan has been scrutinized and objection have been pointed out, the Occupier or owner giving notice shall modify the plan to comply with the objection raised any resubmit it, with the prescribed as mentioned as under 3.9
3.19 Upon the request of the holder of the permit, the authority may issue a temporary Occupancy certificate of occupancy for a building or part thereof before the entire work covered by the permit shall have been completed provided such portion may be, occupied safely prior to full completion of building without endangering life or Public Welfare.
Completion Certificate
Occupancy Certificate
Requirements Of Sites
Proximity Electric Lines
Proximity to Burial or Burning Grounds
Preservation of existing Trees
3.20 The Form of Notice of completion of the erection of a building or the execution of Any work required to be given shall be in the form set forth in appendix-E
3.21 With in a period of 30 days after receipt of the notice of completion referred to in by laws 3.18 the Authority shall communicate in the form set forth in appendix-F The requisite permission to occupied any such building or to use any building or a Part thereof effected by any such work.
6Plinth
Every person, who constructs, re-constructs, add to or alters a building, shall comply with the following requirements.
The ground floor or lowest floor of the building shall be at such level as will allow of the effectual drainage of that floor. Unless the authority, having regard to the circumstances of the case, directs otherwise, the height of plinth shall not be less than 30cm above the ground or site level. Provided that stables, cattle shed, building of similar nature not intended for human occupation who have the plinth and the lowest floor there of , not less than 15 cm above the ground or site level. Unless the authority, having regard to the circumstances of the case directs otherwise.
Byelaw 6.1 shall not apply to a cellar or granary below the ground floor, which is intended for storage only, and
Kitchen Requirements
8
constructed in dry soil or in such manner as to be impervious to moisture.
7Dimensions of Habitable Rooms
7.1 The height of all rooms for human habitation shall not be less than 2.75 meters measured from the surface of the floor to the lowest part of the ceiling bottom of slab in the case of an air conditioned rooms, a height of not less than 2.4 meters measured from the surface of the floor to the lowest point of air conditioning duct or the false ceiling, shall be provided.
Provided that in the case of a sloped roof the height shall not be less than 2.4 meters at any point.
7.2 No habitable room shall have a floor area less 9.50 sq.mt providing that the case of a building having more than on habitable room and the other rooms, at least one room shall have a floor area of 9.50 sq.mtr. and the other rooms shall not have a floor area less than 7.25 Sq.Mtrs 7.3 The minimum width of all habitable rooms shall be 2.4 meters.
Kitchen
8.1 The height of the kitchen measured from the surface of the floor to the lowest point in the ceiling slab bottom shall not be less than 2.75 Mtr.except for the portion to accommodate floor trap of the upper floor.
8.2 The area of the kitchen shall not be less than 5.0 Sq.Mtr.and with a minimum width of 1.8 Mtrs. Where there is a separate store, floor area of the kitchen may be reduced to 4.5 Sq.Mtrs. A kitchen which is intended for use as a dining room also shall have a floor area not less than 7.5 Sq.Mt.with a minimum width of 2.1 Mtrs, provided that in the case of low cost housing, Kitchen may be separated room by itself or it may be part of the multipurpose room. In the case of a regular Kitchen the area should not be less than 4 Sq.Mtrs. with a width of not less than 15 Mtrs.
8.3 Every room to be used as a Kitchen shall have :
(a) Unless Separately provided in a pantry, means for the washing of the Kitchen utensils, which shall be directly or through a sink to a grated and trapped connection to a waste pipe.
(b) An impermeable floor.
(c ) A Hearth with chimney.
(d) The Hearth and the flue must be constructed on non-combustible materials.
(e) The walls of the Kitchen should be at least of two hours fireresistance type. If this is not feasible the Kitchen wall around the hearth and chimney must be constructed of two hours fire resistance type.
Requirements
9.3
Requirements Of staircase
9.6
9.7
9Bath Room and Water Closets:
10.1
9.1 The Height of a bathroom or a water closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be than 2.0 M.
9.2 The floor area of the bathroom shall not be less than 1.8 Sq.M with minimum width Of 1.20 M.
The Floor area of a bath-cum-water closet shall not be less than 2.8 Sq.M. with a Minimum width of 1.2 M.
9.4 The minimum floor area of water closet shall be 1.1 Sq.Mtr. with minimum width of 0.9M.
9.5 Every bathroom or water closet shall:
(a) Be so situated that at least one of its wall shall be open to external area.
(b) Not be directly oval or under any room other than another water closet; washing place, Bath or terrace, unless it has a water tight floor.
(c) Have the platform or seat made of water tight non absorbent material;
(d) Be enclosed by walls or partition and the surface of every such wall or partition wall shall be finished with a smooth impervious material to a height of not less than 1 M.above the floor of such a room; and
(e) Be provided with and impervious floor covering with the slope not running towards verandah or any other room.
(f) Have a window or ventilator opening to a shaft or open space of area not less than 0.3 Sq.mtrs with side not less than 0.3 mtr.
No room containing the water closet shall be used for any other purpose except as Lavatory and no such room shall open directly into any Kitchen or cooking space by a door, window or other opening. Every room containing a water closet shall have a door completely closing the entrance to it.
All Water Closets shall be connected to specific tanks or public sewer to the required sizes and to the satisfaction of the authority
Staircase
All Storeyed Buildings shall be provided with sufficient number of staircases depending on the number of occupants within a distance of not more than 18 mtrs.
10.2 The clear width of all main stairways shall not be less than 100 cm. excluding the Hand rails.
10.3
10.4
10.5
10.6
Ventilation SET BACKS
Passage Giving Access to Staircase
10.0
10.10
Area 11.1
All Stairways shall have at least 2.2m of clear head room measured perpendicularly depending from the nosing.
The minimum width of treads without nosing shall be 25cm. for an internal and main staircase. The treads shall be constructed and maintained in a manner to prevent slipping.
The Maximum height of the riser shall be 19cm. and they shall be limited to 15 per flight.
Hand rail shall be provided with a minimum height of 100 cm.and shall be firmly supported.
10.7 The space beneath any staircase which is built in whole or in part of combustible material except hand rail shall be entirely open.
10.8 In a Public building, no staircase, internal corridor, or Passageway intended for the use of the public shall be less than 2m wide, provided that where not for the use of the more than 200 person are to be accommodated in any public building any staircase; internal corridor or passageway intended for the use of the public may be of any width not less than 1.5m
10.9 In a Public building every staircase, internal corridor or passageway which is intended for the use of the public and communicates with any portions of the intended for the accommodation of more than 400 persons shall be wider than 2 m. by 150 cm.for every 100 persons over 400, subject to a maximum width of 3m.
(A) Every staircase shall be lighted and ventilated from the the open space to the satisfaction of the authority.
Every passage in a building in any floor shall in no part be less than the width of the staircase of such building to which it gives access, provided that, if only one such Passage gives access to mare that one staircase, its minimum width shall be equal to the width of such staircase plus one half of the total width of such staircases plus one Half of the total width of the remaining staircases.
11Lighting and Ventilation
Every room which is intended for human habitation, may be furnished with sufficient no of windows and ventilators totally providing ventilation are of Not less than one sixth of the floor area of the room, affording effectual means of Ventilation by direct communication with the external air.
REAR YARD
11.2
There shall be between the rear boundary of every building site and the building itself an open space exclusively belonging to such building and extending laterally through the width of the site to a depth as mentioned in Bye-Law-12.2.
Provided that where this depth can not be obtained throughout the entire Width of the site by the reason of the exceptional shapes of the site or other exceptional circumstances it shall suffice if the mean depth satisfy the above requirements.
Side Yard
11.3
Only detached buildings shall be permitted within the jurisdiction of Port Blair Municipal Council and there shall be on the either side of every such building An open space as mentioned in the byelaws 12.2.
Front Yard
11.4
Each Site shall be a minimum frontage of 10 meters on any main road or 9 Metre from the edge of the existing roadside drain.
11.5
The front yard for the plots abutting the Branch road shall not be less than 5.00Metres.
11.6
Every building shall have a front yard forming an integral part of the site to a minimum width of 1 meter.
11.7
Every open space provided in pursuance of bye-laws 11.2 to 11.4 shall be kept free from any erection thereon and shall be open to sky, and no cornice roof or whether shade more than 0.75Mt.wide shall overhang or project over the said open space so as to reduce the width to less than the minimum provided under these bye-laws. In case of plots up to 50.00 sq.mtr.the overhang or projection shall not exceed 45 cm.
12. HEIGHT LIMIT
Maximum height Of construction
12.1
The maximum height of a building shall be 10 metres (measured upto the bottom of the beam or the wall plate) unless otherwise specially permitted By the Authority.
Floor area Ratio
12.2
Unless otherwise specially permitted by the authority, the coverage and floor Area ratio for the construction of building in a site shall be as follows:-
Plot Coverage
Plot area in Sq.Mtr.Minimum Set Back
FrontF.A.R
Rear
Side
Side
1
2
Upto 50
75%
1
1.5
0.75
0.75 150
Above 50 upto 100
66.66%
1
1.5
1.00
1.00 150
Above 100 upto 200
60%
1
2
1.00
1.00 150
Above 200
50%
1
3
1.00
1.00 150
Explanation : For working out the Floor area Ratio the area occupied by the Mezzenine Floor Shall also be included.
13 Width of Doors and Passages
Minimum width Of entrance and Door way
13.1 No doorway or corridor or Passage serving as an entrance or exit to a building shall be less than 1 Metre in width . Doorways shall not be less 2.00M in height.
13.2 The doors of a Kitchen, Bath, and water closet shall not be less than 0.75cm.clear in width and the passage leading to the same shall not be less than 75cm.
14 Parking and Parking Facilities:
Parking space Requirement
14.1 For the use of occupants and of persons visiting the premises for the premises for the purposes of profession trade, business, recreation, or any Other work, parking space and parking facilities shall be provided within the site Conforming to the standards specified in Appendix-‘H’ to these byelaws.
14.2 Necessary provisions shall be made for the circulation of vehicles gaining Access to and from (i) The parking spaces and facilities and
(ii) The premises in to the street.
15Orientation of Building
(A) Construction of building in vicinity of Airfield.
(i) No Building or structure shall be constructed or erected or no tree shall be planted in the Vicinity of the Airfield without the clearance from Airports Division.
(ii) The construction of any building or structure in the vicinity of Airfield may be permitted after obtaining ‘No Objection Certificate’ from Airports Authority of India, National Airports Division.
(iii) Every person who intends to construct reconstructs alter or add to a building shall apply to the authority for obtaining NOC from National Airport Authority in the forms and proforma in appendice I,IIA,IIB,IIC,IID,&IIE.
(iv) An applicant may represent for reconsideration in cases where the application has been rejected or allowed with restrictions. Such representations should be sent to appropriate Officer of the National Airport Authority.
(v) Validity of the NOC issued will be for a period of 2 years only from the date of issue. If the building or structure is not completed within this period the applicant is required to apply a fresh.
(B) Coastal Zone Management Plan.
The Port Blair Municipal area has been re-grouped as CRZ-(ii) and existing local Town and Country Planning Regulations are applicable to this area as per clause-2 (v) cad with CRZ-(ii) (1) of the Govt.of India’s Notification dated 19/02/1991. Hence all constructions within the Municipal Area shall confirm to the CRZ Notification of 1991.
Architectural Control
(i) Buildings shall be permitted neither on the seaward side of the existing road ( or roads proposed in the approved Coastal Zone Management Plan of the area) nor on seaward side of existing authorized structures, buildings, permitted on the landward side of the existing and the proposed road existing authorized structures shall be subject to the existing local town and country planning regulation including in the existing norms FSI/FAR.
(ii) The Reconstruction of the authorized buildings to be permitted subject to the existing FSI/FAR norms and without change in the existing rules.
(iii) The design and construction of buildings shall be consistent with the surrounding landscape and local architectural style.
16ARCHITECTURAL Control.
1 Every person who constructs, reconstructs adds to or alters a 6 building With a sloped roof, shall cause such roof portion open, to sky to be painted with chocolate colour.
1 Every person who constructs, reconstructs adds to or alters a 6building With a sloped roof, shall cause the visible area of eaves board of Such roof to be painted with white colour.
1The appearance of all verandah, advertising signs and similar 6 projections shall be subject to the approval of the authority having jurisdiction, who may demand that such existing 3 structures to be altered when necessary at the owner’s expenses so as to confirm harmoniously with the neighbouring areas.
1No building will be left with unfinished portions including 6projecting reinforcing bars, which is in the opinion of the authority are unsightly, unless with the permission of the
4 authority who may prescribed conditions with respect to the structure and the period for which such permissions remain valid.
16.5 As soon as any building is completed, all rubbish, refuse or debries of any description shall be removed by the owner from the site or sites on which building operations have been have been carried out or from any adjoining land which may have been used for deposition of of materials or debris.
16.6 All Wires, poles, Maste, stays structs, lighting conductors, and similar fixtures on new building shall be straight and of good appearance.
16.7 Permanent dumps of scrap-iron, firewood, coal and similar materials shall in all areas except those classified as factory areas, be allowed only in places enclosed with walls of non combustible materials.
16.8 The use of any disfigured or damaged material, which in the opinion of the authority results in an unsightly appearance or a building shall not be allowed.
Exit Requirements.
16.9 In case of Parks or Gardens, visible from the streets, the owner of such park or garden shall not plant, replace or maintain trees or plant , which in the opinion of the Authority conflict with the aesthetic disfigurement of the neighborhood.
16.10 Where several facades constitute architectural composition, painting or such other treatment shall only be allowed where no aesthetic disfigurement can result to the composition as a whole
16.11 Every person who constructs, reconstructs adds to or alters a building unless or otherwise specially permitted by the Authority, shall cause the building to be oriented based on sunlight and wind direction and in such a manner that the façade of the building is as far as possible situated parallel to the street in front.
17 Protection Against Earthquake:
Every person, who constructs, reconstructs adds to or alters a building shall cause the design of the structure made safe for the components of earthquake vibrations as per requirements of seismic Zone-V. Classified by the National Building Code.
18 Fencing
Every building site may be fenced suitably either with live fencing or a compound wall. No such fencing or compound wall shall have a Height more than 1.5metres from the ground level.
19 Splay
In the case of plots located at the corner of two streets, the fencing prescribed in the bye-laws 18 shall splayed as prescribed here under:
for streets with width of more than 12M-3MX 1M splay, provided that in case of corner of two streets of different widths the ruling shall be taken as that of the wider street.
5Foundations
The foundation of every building or structure shall be so designed and constructed so as to sustain the dead load of the building and the live load and to transmit and distribute loads over the soil in such a manner that pressure brought to bear on the soil buy these load does not exceed the safe bearing capacity of the soil.
The foundation shall be taken down to such a depth or so constructed as to render the building immune from damage from movement due to seasonal variation in the content of moisture in the ground.
5.3 The design and construction of foundation shall confirm to the appropriate Indian Standard Specification.
Every person who constructs, reconstructs, adds to, or alters a building shall take such steps, do such things as the authority may direct or require so as to secure proper stability of the building and to render the building immune from any settlement of movement that may be caused in the soil sliding of the sub-stratum on sloping ground distributed on concentrated laterial pressure or other causes.
Licence FEE 3.5(d)
A Registration/ Licence fee as prescribed in Appendix-‘K’ shall be charged for enlistment with the Municipal Council as Licensed Architect, Licenced Engineer, Licence Supervisor as the case may be.
3.6 Every Person, who intends to erect a building or execute any such work shall get its structural work designed by
(a) A registered Architect or Regd. Engineer in the case of RCC & STEEL structures for more then two storeyed residential buildings.
(b) A licenced supervisor in other cases.
3.7 No notice and building permit is necessary for the following alterations which do not otherwise violate any provisions regarding general building requirements structure stability and fire safety of the bye-laws:-
(a) Opening and closing of a window or door or ventilator;
(b) Providing intercommunication doors;
(c) Providing partition;
(d) Gardening;
(e) White Washing;
(f) Painting;
(g) Plastering and patchwork;
(h) Reflooring;
(i) Construction of sunshade; and
(j) Re-erection of portions of building damaged by earthquake or other natural calamities, to the same extent and specification as existed prior to such damage.
20Exit
20.1 Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants in case of fire or other emergency.
20.2 Every exit doorway shall open into an enclosed stairway, a Horizontal exit, on a corridor or passage way providing continuous And protected means aggress.
20.3 No exit doorway shall be less than 100cm in width and 200cm in Height.
Requirement of Corridors and Passage.
Special Hazards
20.4 Exit door shall not open immediately upon a flight of stairs; a landing equal to at least the width of the door shall be provided in the stairway at each doorway. Level of landing shall be the same as that of the floor, which it serves.
21 Corridors and Passageways.
21.1 Exit Corridors and Passageways shall be of width not less than 1mtrs.
21.2 Where Stairways discharge through corridors and passageways, the Height of corridors and passageways shall be not less than 2.4m.
22Fire Escapes.
22.1 Every building with more than one floor shall have a “Fire Escape” stair which shall be directly connected to the ground.
22.2 Entrance to fire escape shall be separate and remote from the internal staircase.
22.3 The route fire escape shall be free of obstructions at all times, except a doorway leading to the fire escape which shall have the required life resistance.
22.4 Fire escapes shall have straight flights not ,less than 75 cm wide with 20cm tread and risers not more than 19cm. The number of risers shall be limited to 15 per flight.
22.5 The use of spiral staircases shall be limited to low occupant load and to a building of height not more that 9m unless they are connected to the platform such as balconies and terraces.
22.6 A spiral fire escapes shall not be less than 150 cm. in diameter and shall be designed to dive adequate head room.
23Special Hazards
23.1 Flammable liquids for house hold purposes shall be kept in tightly Stoppered or sealed containers
23.2 No stove or combustion heater shall be located directly under or immediately at the foot of stairs or otherwise so located as to block escape in case of malfunctioning of the stove or heater.
23.3 Doors leading into rooms in which flammable liquids are started or used shall be self closing and shall be posted with a sign on each side of the door in 25mm high block letters starting.
“fire Door Keep Close”
Requirements for 24. All Public Buildings shall be provided with approved Public Buildings manually operated fire alarm facilities and shall be tested daily.
26.1
Requirements of Chimneys and Flues
27.2
Fire Resistance Rating
28.1
Every hospital shall be equipped with a communication system, suitable for alerting all persons charged with the duties for patient care, and all employees of the hospital who are within the building in the event of emergency. The alerting system shall be capable of being operated from the telephone switch board and the Administrative Office.
26Chimneys and Flues:
All Heating and cooking appliance bring solid, Liquid or gas fuel shall be connected to and have their products of combustion removed by a chimney or flue.
26.2 The Height of Chimneys and flue shall be
(a) not less than 60cm on above roof if they penetrate the same.
(b) not less than 60 cm higher than any part of the building coming within horizontal radius of 15 cm. of the Chimney.
26.3 A Clearance of at least 4cm shall be provided between the outer surface of a chimney and any adjacent combustible material forming part of a wall lining enclosing the chimney.
26.4 Combustible material in the adjoining structure of a building shall not be allowed to come into contact with the chimney.
26.5 The material of which the Chimney is made shall be able to withstand the temperature reached by the flue gases and other deleterious effect associated with the burning of fuels.