Building‐units for use as Fueling & eV Stations shall comply with Petroleum Rules 1976 under the Petroleum Act 1934 and electric charging station established under Electricity Act-2003.
10.1 Area of Building unit and Frontage
The minimum area and frontage of a Building‐unit for a Fuelling & eV Station or Fuelling & eV with Service Station shall be as specified in table 10.1.
| Sr.No. | Fuelling &eV Station Type | Minimum Area of Building-unit sqmts. | Minimum Frontage on Road Side mts. |
| (1) | (2) | (3) | (4) |
| 1 | Fuelling &eV Station(without Service Station) | 500 | 16.5 |
| 2 | Fuelling &eV with Service Station | 2000(other than category D7(B),D8 &D10) | 30mts |
| 500(for category D7(B), D8 &D10) |
10.2 Location
-
Fuelling &eV Station may be permitted only on Road width of 18mts and more in any Zone.
-
The location of Fuelling & eV Station or Fuelling & eV with Service Station shall be at a distance of 50mt, away from the junction of two or more roads among which one of them is wider than 18 mt. and it shall be 30 mt in case of other junctions. The minimum distance shall be computed from the boundary line of the Building‐unit to the edge of the road as indicated in the illustration.
-
In the case the Station is provided along a main road which has a service road or a marginal access road, the access to the Station should be provided from the service road or the marginal access road and not from the main road.
10.3 Maximum Permissible Ground Coverage
Irrespective of general provision of any zone Maximum Permissible Ground Coverage for Fuelling &eV Station and Fuelling &eV with Service Stations shall be 45% of the Building‐unit including the area of the canopy.
10.4 Margins
10.4.1 For Fuelling &eV Station:
-
Road side margin from canopy to the plot boundary shall be as per Planning Regulation 6.7 subject to minimum 6.0mts. On all other sides, margin from canopy to the plot boundary shall be 4.5mts and 6.0mts in the case of canopy having height up to 6.0mts and more than 6.0mts from ground level respectively.
-
Marginal distance from curb site (Fuelling &eV Pedestal) to the plot boundary towards main road shall be minimum 9.0mts and for other sides of the plot, it shall be 6.0mts.
-
Administrative building for the petrol pump shall have minimum road side margin as per planning regulation 6.7; minimum side and rear margin of 3.0mts and as per Planning Regulation 6.7. Zero margins can be provided towards canopy but minimum 6.0mts clear drive way shall be provided to any curb site.
-
Minimum 6.0mts clear drive way shall be maintained between every curb site (Fuelling &eV pedestal).
-
Minimum width of access road shall be 6.0mts.
10.4.2 For Fuelling &eV Station with Service Station:
-
Road side margin from canopy to the plot boundary shall be as per Planning Regulation no. 6.7 subject to minimum 6.0mts and all other sides shall be 6.0mts. Provision of above (2) and (4) in Planning Regulation 6.7 will remain the same.
-
While building of service station can have zero margins towards canopy, subject to minimum 6.0mts towards road side and 3.0mts towards other sides of the plot.
-
Clear 6.0mts drive way between curb site (Fuelling &eV pedestal) and service station building shall be provided.
-
Minimum width of access road shall be 6.0mts.
10.5 Height, Floor Space Index & Common Plot The maximum allowable height shall be 7.5mts and FSI shall be according to the relevant zone. Also common plot shall not be required.
10.6 Parking
Every Fuelling & eV Station and Fuelling &eV with Service Station should provide minimum parking spaceson the basis of the Building unit Area as stated in the table below:
| No | Fuelling &eV station (area in sq.mts.) | Minimum parking requirement |
| (1) | (2) | (3) |
| 1 | 500 | 3 cars and 5 two-wheelers |
| 2 | 2000 (other than category D7(B) and D8) | For every 500 sq.mts more than 1000sq.mts, additional parking for 1car and 2 two-wheelers shall be required. |
| 500 (for category D7(B) and D8) |
10.7 Basement
No basement shall be allowed.