Regulation 24 of the principal regulations, shall be substituted by the following, namely:- "24.Distance from Electricity Lines:
No roof of a building shall be made, and no verandah, balcony or the like shall be allowed to be erected or re-erected or new addition or alteration made to a building within the distance quoted below in accordance with the Central Electricity Authority(Measures Relating to Safety and Electric Supply) Regulations, 2010:-
| Sl.No | Voltage Level | Distance between Line and Building | |
| Vertical | Horizontal | ||
| 1 | Upto 650 V | 2.5 m | 1.2 m |
| 2 | Exceeding 650V upto and including 33 kV | 3.7 m | 1.2 m (for 11 kV line)2.0m(for 33kV line) |
| 3 | Exceeding 33kV | 3.7m(plus 0.3m for every additional 33kV or part thereof) | 2.0 m (plus 0.3m for every additional 33kV or part thereof) |