- Application for Fire Safety Certificate.—(1) Every owner or occupier of any high-risk building shall submit an application in Form E through a licensed agency for Fire Safety Certificate to the Director-General/or superior nominated authority every calendar year together with the documents mentioned therein and a requisition for fire safety of the licensed agency duly recommending the application.
[Rr. 16-19]
(2) A licensed agency shall receive and process applications in Form E for issue of Fire Safety Certificate to the owners or occupiers of a high-risk building, subject to the fulfilment of the conditions laid down in the Act and these rules.
(3) The licensed agency, on being satisfied, shall recommend the application to the Director-General or superior nominated authority with a requisition for fire safety listing the fire safety and fire prevention measures adopted by the applicant.
-
Issue of Fire Safety Certificate.—On receiving the application in Form E and the related documents, the Director-General or the superior nominated authority, being satisfied with the adequacy of fire prevention and fire safety measures in respect of the high-risk building, shall issue a Fire Safety Certificate in Form F on payment of fee at the rate '[as specified in the Schedule to these rules].
-
Subs. by Notification No. 467/DS/FES/N/C-1/1A-1/2005 dated 14.01.2005 for "of 10% of the annual value of such building".
-
Rates of special rate
-
Rates of special fee for obtaining no objection certificate in respect of high-risk building.—¹[(1) The person or association of persons intending to construct a high-risk building shall pay the special fee at the rates as specified in the Schedule to the
(1A) The person or association of persons owning a high-risk building on or before the date of coming into force of this notification, shall pay the special fee at the rates equivalent to half of the rates specified in the Schedule as stated in sub-rule (1).]
(2) The special fee is to be deposited through T.R. Form No. 7 under the receipt heads of the Fire Services within fifteen days of intimation from the Director-General or the superior nominated authority regarding the amount to be paid. No objection certificate shall be issued on depositing the original receipted challan with the
(3) The issue of no objection certificate shall be governed by the relevant conditions laid down for issuing of Fire Safety Certificate in rule 19.
-
Subs. by Notification No. 467/DS/FES/N/C-1/1A-1/2005 dated 14.01.2005 for "(1) The person or association of persons intending to construct a high-risk building shall pay an additional percentage of the building fee imposed by the local civic authority as a special fee at the rates as specified in the schedule to these rules".
-
Period of validity of a Fire Safety Certificate.—Any Fire Safety Certificate shall remain valid for a period of one year with effect from the date of issue of the Fire Safety Certificate.
-
Conditions for issue of Fire Safety Certificate.—Any high-risk building shall conform to any or all of the following conditions,
R. 19]
65
and/or the conditions laid down in Part IV of the National Building Code, Indian Standard specification and relevant building rules, as the licensed agency may deem expedient with special reference to the degree of hazard involved for obtaining a Fire Safety Certificate:
(a) in the case of a building for storage of petroleum or petroleum product including kerosene, it shall comply with the provisions of the Petroleum Act, 1934 (30 or 1934);
(b) the building shall not be situated in a densely populated area where it would be a nuisance to the inhabitants of the neighbourhood;
(c) the building shall have the clear open space subject to provisions of the relevant building rules, of the relevant local authority, in force;
(d) the engines, furnaces and ovens shall be at a safe distance from the places where inflammable articles are stored or processed or proposed to be stored or processed;
(e) no article referred to in clause (h) of section 2 of the Act shall be stored or processed on the top or on the roof of any such building;
(f) the building shall maintain any or all of the following minimum standards for fire prevention and fire safety as the licensed agency may deem expedient:
(i) ways of access,
(ii) underground or overhead water static tank exclusively for fire fighting with replenishment arrangements,
(iii) adequate number of portable fire extinguishers,
(iv) pressure fed hydrant within the perimeter of the building,
(v) fire engine trailer pump of 500 G. per minute capacity,
(vi) first aid hose reels,
(vii) proper compartmentation,
(viii) automatic fire detention and alarm system, or manually operated electrical fire alarm system, or both,
(ix) proper public address system,
(x) illuminated exit way marking system,
(xi) alternate source of electric supply,
(xii) fire lift with fireman switch,
(xiii) rising main with landing valve,
(xiv) proper safety measures for electrical installations,
WBFS-5
[Rr. 19A-20]
(xv) adequate means of escape,
(xvi) floor number signs,
(xvii) dampers and other safety measures in air-conditioning system,
(xviii) fire notice, and
(xix) other general recommendation of National Building Code Part IV.
¹ [19A. Employment of professionally qualified fire personnel.—Any high-risk building shall have a professionally qualified fire personnel.
Explanation I.—For the purpose of this rules, the expression “high-risk building” means—
(a) any residential building or building complex having one hundred or more number of occupiers;
(b) any business house, mercantile house, multiplex, mixed occupancy building, amusement park, technology park or other public assembly buildings having the total floor area of five thousand square meter or above;
(c) any hotel of three star category or above resort, club having different activities with bar and restaurant facilities;
(d) any other high-risk building in which the service of a professionally qualified fire personnel is necessary for the interest of public safety.
Explanation II.—For the purpose of this rule, the expression “professionally qualified fire personnel” means a fire personnel who has passed sub-officers course from the National Fire Service College, Nagpur or the certificate course in professional fire fighting from the Institute of Fire Service, West Bengal, or equivalent 1.
-
Ins. by Notification No. 467/DS/FES/N/C-1/1A-1/2005 dated 14.01.2005.
-
Manner of mock fired drill, 1983, 1984.
-
Manner of mock fire drill and issue of certificate.—(1) The occupiers of all high-risk buildings shall, in the presence of a licensed agency carry out a mock fire drill, in every year, involving all occupants of the building and the watch and ward staff of the building under prior intimation to the Director-General or the superior nominated authority.
(2) The fire drill shall be conducted following the guidelines as laid down in Appendix D in Part IV of the National Building Code. (3) The licensed compound building
(3) The licensed agency shall issue a certificate of performance of the mock fire drill in the form specified in Form G and the occupier of the concerned high-risk building shall furnish such certificate to the
Rr. 21-23]
67
Director-General or the nominated authority and maintain a register in this behalf.
- Inspection of buildings or premises.—(1) The Director-General or the superior nominated authority or licensed agency authorised in this behalf, as the case may be, may enter and inspect any building or part thereof or any premises at any time between sunrise and sunset where such inspection appears necessary for ascertaining the adequacy or contravention, if any, of fire prevention and fire safety measures referred to in the Act or these rules.
(2) A notice, if the Director-General or the superior nominated authority considers necessary, may be served to the owner or occupier of the premises, where the Director-General, or the nominated authority intends to enter and inspect, in Form H at least 3 hours before such entry.
(3) If the Director-General or the superior nominated authority is satisfied that owing to inadequacy of fire prevention and fire safety measures the condition of any high risk building or part thereof is in imminent danger to person or property, then, he or it may, before proceeding in accordance with section 37, issue a notice and display the same in writing in the manner as he thinks fit.
- Revocation of Fire Safety Certificate.—The Director-General or the superior nominated authority may revoke any Fire Safety Certificate without prejudice to any action that may be taken against him under section 11C of the Act in the event of—
(a) non-compliance with any notice served under section 35 of the Act without prejudice to any action taken under section 36 of the Act; or
(b) non-compliance with mock fire drill, specified in rule 20 of these rules in any year.
- Manner of carrying out work of providing fire prevention in a high-risk building.—(1) No person, other than a licensed agency, shall carry out and perform the work of fire prevention and fire safety measures or such other related activities as required to be carried out in any high-risk building.
(2) While carrying out the work specified in sub-rule (1), the licensed agency shall maintain a register for each high-risk building, in duplicate, in the manner specified in Form I and one copy of such register shall be kept with the owner or occupier of the building which shall be shown to the Director-General or the superior nominated authority, as and when required.
[Rr. 24-29]