No.11/2/70-UTFI(4)-2019/ 20494 In partial modification of the notification issued by the Finance Department, Chandigarh Administration vide no. 11/2/70-UTFI(4)-2017/ 6994A dated 25.07.2017 as amended vide notification bearing No. 11/2/70-UTFI(4)-2019/11142 dated 12.07.2019 and in exercise of the powers conferred under Section 4, Section 5(2) and Section 22(1) of the Capital of Punjab (Development & Regulation) Act 1952 as adapted by the Punjab Re-Organization (Chandigarh Adaption of Law on State and Concurrent Subject) Order, 1968 for the Union Territory of Chandigarh and all other powers enabling him in this behalf, the Administrator, Union Territory, Chandigarh, is pleased to make the following Rules to further amend the Chandigarh Building Rules (Urban)-2017, as under :-
-
Title, Extent and Commencement:- These Rules may be called "Chandigarh Building (Amendment) Rules (Urban)-2019".
-
These Rules shall come into force from the date of their publication in the Official Gazette of Chandigarh Administration.
-
That in the Chandigarh Building Rules (Urban)-2017, the Rule 5.1.12 as existing, shall be substituted as under:-
"5.1.12 Basement
i) Basement shall be optional or as specified in the applicable Architectural Control.
ii) Non habitable use shall be allowed only for Storage, Services and utilities w.r.t. building infrastructure. Minimum height 2.4 m (8'-0") below the beam/ roof slab is free from FAR.
iii) No basement is allowed in booths.
iv) In case existing adjacent building is constructed without basement, a minimum setback of 2.4 m (8'-0") shall be taken from the existing adjacent building subject to the fulfilment of structural stability to be ensured by the registered Structural Engineer."
- That in the Chandigarh Building Rules (Urban)-2017, the Rule 5.1.18 as existing, shall be substituted as under:-
“5.1.18 Maximum 4 Sub divisions allowed to be occupied by different tenants/outlets, on each floor of a single bay shop with a minimum of 6 ft. wide corridor and up to 8 partitions on a floor of double bay shop with 9 ft. wide corridor where there are offices on both sides of its subject to provision of adequate forced fresh air circulation. To simplify procedure, owner should only be required to submit the layout and deposit prescribed fee with Estate Office.
The partition wall between the sub divided shops shall be of any fire retardant material and constructed maximum up to ceiling height.
It is clarified that subdivisions shall be allowed on each floor for office use, in case use of the SCF/SCO has been got converted into SCS (shop-cum-shop) then single unit / single shop by a single user shall be allowed.
- That in the Chandigarh Building Rules (Urban)-2017, the Rule 11.1.4 as existing, shall be substituted as under:-
“11.1.4 If during the construction of a building, any deviation from the sanctioned plan is intended to be made, approval of the Competent Authority for the same may be obtained before the change is made. The revised plan showing the deviations shall be submitted and the procedure laid down for the sanction of building plan as stated in Rule
11.1 and 11.1.2 shall be followed, along with depositing of required fee, if any. Provided, that revised building plans in continuation to the originally sanctioned building plans can only be submitted once. Non compoundable/ Non sanctionable deviations beyond Zoning may not be considered at any stage and these will have to be removed before processing any building plan application."
- That in the Chandigarh Building Rules (Urban)-2017, the Rule 11.1.9 as existing, shall be substituted as under:-
"11.1.9 Building Plan once approved shall be valid for completion of construction within a period of 5 years".
It is clarified that prior to revalidation of building plan, status of the existing construction at site has to be taken by the Estate Office/SDO (B). If the building is under construction as per the sanctioned plan then the revalidation of building plan shall be considered as per rules. If planning is changed w.r.t. the sanctioned plan then no revalidation of plan shall be permitted and the owner may be asked to submit the revised building plan as per the prevailing building rules."
- That in the Chandigarh Building Rules (Urban)-2017, after the Rule 10.8 as existing, the following new Rules 10.9 & 10.10 shall be added as under:-
"10.9 Provisions in Commercial Buildings (SCO's/ SCF's/ Bay Shops & Similar Buildings).
10.9.1 SUB DIVISION subject to the prior approval of the Estate Office/Municipal Corporation, Chandigarh.
10.9.2
The erection of partitions in Multi bay ground floor shops for the purpose of independent usage of each partitioned space shall be allowed in accordance with the building bye- laws.
A. In the City Centre, Sector 17 (RCC frame), maximum 4 subdivisions of 2 bay shops of size 34'-6" x 103'-0" shall be allowed at ground floor only. In three bay shops, maximum number of sub divided shops shall be 6.
B. Two subdivision of 3 bay shops (brick face), measuring 33'-o" x 80'-o" i.e. shopping strip V4, Sector 17 shall be allowed at ground floor only. The position of mezzanine floor shall not be altered and shall be subdivided in case of subdivision is opted for. The sub-divided mezzanine floor shall be approached independently through separate stairs from the subdivided portion of the shop.
C. In case of shops having verandah on both sides, only one sub-division shall be allowed and the minimum size of sub-divided shops shall be 16'-6" x 35'-0" inclusive of verandah.
D. Two subdivision of multi bay shops at ground floor in other location in Chandigarh except Sector-17 shall be allowed.
The above provisions shall be allowed subject to the following conditions:-
i) The ownership of the shop shall not be changed.
ii) The sub-divided shops shall not be transferred by way of sale gift, mortgage, will/ power of attorney of otherwise.
iii) An additional entry with door shutter opening may be provided subject to the condition that ventilation for the basement floor in the remaining part of the glazing is not disturbed. However, the size of the additional entry shall be of the same size as that of existing entry.
iv) An additional door in the rear side of the building of the same width/ height and design as that of the existing door on the rear side will be allowed as shown in the Architectural Control Sheets.
v) The partition wall between the sub divided shops shall be of any fire retardant material and constructed maximum upto ceiling height.
vi) The partitions for subdivisions shall be allowed only along columns & under the beams.
vii) It is clarified that need-based partitions required for the needs of single user of the entire ground floor space such as office, bank, departmental store etc. shall not be subject to any charges. In such cases it shall be ensured that the entire floor has an open floor plan and is designed to function as single unit.