27
(See rule 36)
License of Fire and Life Safety Auditor.
License No. Date :
Licence is hereby granted or renewed under the provisions of section 45A of the Maharashtra Fire Prevention and Life Safety Measures Act, 2006 (Mah. III of 2007) to having registered office at to act as a Fire and Life Safety Auditor for the purposes of the said Act for evaluation of the fire prevention and life safety measures in buildings or parts thereof for ensuring that the fire fighting systems are in good repair and efficient working condition.
The license shall be valid for a period of two years from the date of issue i.e.from till
Director
Maharashtra Fire and Emergency Services.
Form ‘Y’
(See rule 37)
Notice for suspension or cancellation of Fire and Life Safety Auditor License To,
Whereas a License of Fire and Life Safety Auditor for the purpose of the Maharashtra Fire Prevention and Life Safety Measures Act, 2006 (Mah. III of 2007) and the Maharashtra Fire Prevention and Life Safety Measures Rules, 2009 being a license No dated has been granted or renewed in the name of
And Whereas the following contraventions and irregularities have been noticed, namely :—
(1)
(2)
And Whereas these acts amount to
Now, therefore, in exercise of the powers conferred on me under sub-section (6) of section 45A of the said Act, I, hereby call upon you to show cause in writing so as to reach the undersigned on as to why the license so granted or renewed in your favour should not be suspended or cancelled.
Director
Maharashtra Fire and Emergency Services.”.
- After Form Y, the following Appendix shall be added, namely :—
“appendix
[See rule 4(3)]
-
Automated Continuous Monitoring System (ACMS) based on Internet of Things (IoT) for the fire fighting system in a building or part thereof as specified under section 45 of the Act shall be provided for both Active and Passive Measures, ensuring that the fire prevention and life safety measures are in good repair and efficient working condition.
-
The provision of the ACMS shall be done in two phases. The installation of ACMS shall be such that it will give necessary indication to both the owner or occupier as well as the system installer i.e. licensed agency as appointed under section 9 of the Act in the first phase. In the second phase, the critical alarms shall also be sent to the local fire and emergency services. Details regarding process required in both the phases is given in clause 4. The initiation of the Phase I shall be done with immediate effect of the rules coming in force whereas phase II shall be done at later stage.
-
The ACMS shall be provided as under :—
(a) System Status.—The system shall be integrated with requisite mechanism enabling to know the status of each system which shall be generated and collected on any suitable IoT Gateway. The data collected then shall be then uploaded on any suitable Cloud server which will then send requisite real time information of the system health to owner / occupier and the system installer on email, short message service (sms) or on mobile through any suitable app service. Status of following systems shall be notified.
(b) Hydrant :—
(i) Main Hydrant Pump run status.
(ii) Standby Diesel/Electrical Pump run status.
(iii) Diesel tank level Monitoring.
(iv) Power to Main Hydrant Pump (On / Off).
(v) Hydrant riser low pressure monitoring.
(vi) Jockey Pump run status.
(vii) Power to Jockey Pump (On/ Off).
(viii) Booster pump Pump run status.
(ix) Power to Main Booster Pump (On/ Off).
(c) Fire Water Tank :—
(i) Underground / Aboveground Fire Tank Level Monitoring.
(ii) Overhead Tank Low Level Monitoring.
(d) Sprinkler :—
(i) Main sprinkler Pump run status.
(ii) Power to main sprinkler pump.
(iii) Sprinkler riser low pressure monitoring.
(e) Detection System :—
(i) Detection operation status (On/ Off ).
(ii) Control Panel / Repeater Panel status (working / non-working).
(iii) Battery of Control Panel status.
(f) Manual Call Points.- Manual Call Points operation Status (On/ Off).
(g) Public Address System: Public Address System status (working / non working).
(h) Air Pressurization.—
(i) Staircase Pressurization Fan run status for all exits Lift Lobby/ Hoistways.
(ii) Pressurization Fan run status for all Lift Lobby/ Hoistway.
(i) Supply and Exhaust Fan.- Basement supply and Exhaust Fan Run Status for Ventilation or Exhaust system.
Note.—Following Data parameters will be monitored and will be send from local Gateway to Cloud Portal for Real time monitoring and Report Generation.
I. Mode of Integration :
| Sr. No. | Monitoring of Critical Fire and Life Safety Parameters | Mode of Integration |
|---|---|---|
| 1.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.17.18.19.20. | Main Hydrant Pump run status Main Sprinkler Pump run status Standby Diesel / Electrical Pump run status Jockey Pump run status Booster Pump run status Diesel tank low level Monitoring Power to Main Hydrant Pump Hydrant Riser Low Pressure Monitoring Power to Main Sprinkler Pump Sprinkler Riser Low Pressure Monitoring less than 5 Bar UG / AG Fire Tank Low Level Monitoring System Overhead Tank Low Level Monitoring System Detection Operation Status Control Panel / Repeater Panel status Battery of Control Panel status Manual Call Points operation Status Public Address (PA) System status Staircase Pressurization Fan run status for all Exits Lift Lobby/Hoistway Pressurization fan run status Basement Supply and Exhaust Fan run status for Ventilation/Exhaust system | Water Differential Pressure Switch Water Differential Pressure Switch Water Differential Pressure Switch Water Differential Pressure Switch Water Differential Pressure Switch Level Sensor Voltage Sensor at Motor Control Centre (MCC) Pressure Switch/ Transmitter Voltage Sensor at MCC Pressure Switch/ Transmitter Ultrasonic water level device Ultrasonic water level device Plain Old telephone Service (POTS) free contacts from fire panel Plain Old telephone Service (POTS) free contacts from fire panel Plain Old telephone Service (POTS) free contacts from fire panel Plain Old telephone Service (POTS) free contacts from fire panel Fault Status for PA panel Air Differential Pressure Switch Air Differential Pressure Switch Air Differential Pressure Switch |
- Procedural Requirements.—The main objective of the IOT base system is to ensure that fire prevention and life safety systems provided in buildings are maintained in good repair and efficient working condition for,—
(a) Digital Monitoring the Operations of the Fire Fighting Installation and Equipment;
(b) Digital Maintenance and Record Keeping of Fire Fighting Installation and Equipment.
These can be achieved by adopting following procedure guidelines,—
(i) Providing minimum Digital Inputs and Analog Inputs depending upon the system requirement.
(ii) Machine to Machine communication by following MQTTS Protocol which will send the Data. MQTTS Protocol to send the Data to cloud portal on real time basis.
(iii) Connectivity to Cloud Using 4G/5G and above or Ethernet or WiFi or any other reliable wired or wireless medium which will receive data from IoT gateway at every 1 min interval.
(iv) Cloud will also send an alarm via SMS if no data is received from the IoT gateway for more than 15 mins. Cloud portal should generate alarm in case data is not received for more than specified time so we can ensure reliability on IoT system.
PRIYANKA KULKARNI-CHHAPWALE, Deputy Secretary of Government.
ON BEHALF OF GOVERNMENT PRINTING, STATIONERY AND PUBLICATION, PRINTED AND PUBLISHED BY DIRECTOR, RUPENDRA DINESH MORE, PRINTED AT GOVERNMENT CENTRAL PRESS, 21-A, NETAJI SUBHASH ROAD, CHARNI ROAD, MUMBAI 400 004 AND PUBLISHED AT DIRECTORATE OF GOVERNMENT PRINTING, STATIONERY AND PUBLICATIONS, 21-A, NETAJI SUBHASH ROAD, CHARNI ROAD, MUMBAI 400 004. EDITOR : DIRECTOR, RUPENDRA DINESH MORE.